Superior Fireplaces DRT2040REN-C Installation And Operation Instruction Manual page 26

Direct-vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
DRT2000-C Series Direct-Vent Gas Fireplaces
Vertical (Offset) Installation
1. Analyze the vent route and determine the number of vent sections and elbows required—See Effective Vent
2. Frame the ceiling opening—Use a plumb line from the ceiling above the fireplace to locate the center of the
Figure 19 - Framing the ceiling opening
Roof
Framing
3. Attach the vent components to the fireplace—See Connecting the vent pipe on Page 23.
4. Attach the vent components to each other—See Connecting the vent pipe on Page 23.
5. Install firestop/spacer at ceiling—When using Secure Vent
6. Support the vertical vent run sections—Support the vertical portion of the venting system every 8 ft (2.4 m)
Figure 20 - Supporting the Vertical Vent Run
26
Length on Pages 23-24 for more information. Plan the venting so that a joint does not occur in the ceiling or
roof joists. Allow for elbows (Figure 17, Page 23). Maintain clearances to combustibles equal to or greater than
minimum specified in these instructions.
vertical run. Cut and/or frame an opening, 10-1/2 x 10-1/2" (267 x 267 mm) inside dimensions, about this center
mark (Figure 19).
10-1/2" (267 mm)
minimum 10 1/2 in.
minimum 10 1/2 in.
10-1/2" (267 mm) minimum
(267 mm)
Plumb Bob
Ceiling
Framing
using Secure Flex
, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/
®
spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer
must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the
firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (26 mm) clearance to combustibles, framing members, and attic or ceiling insulation
when running vertical chimney sections. The gap between the vent pipe and a vertical firestop can be sealed with
non-combustible caulking.
NOTE: Attic Insulation Shield (H3907) must be installed when blown or loose-fill insulation is used, and is
required for all attic installations.
above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional
plumber's tape). Secure the plumber's tape to the framing members with nails or screws. Loop the tape around
the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent pipe (Figure 20).
NOTE: Proper venting support is very important.
Blocking
Support straps
(plumber's tape)
8 ft (2.4 m)
maximum
1/2" (13 mm)
minimum
clearance to
combustibles
minimum
(267 mm)
, use SV4.5VF firestop/spacer at ceiling joists; when
®
Installation
900948-00E, 07/2020