DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE
INSTALLATION
Continued
INSTALLING GAS PIPING TO
FIREPLACE LOCATION
WARNING: A qualified ser-
vice person must connect fire-
place to gas supply. Follow all
local codes.
CAUTION: For propane/LP
units, never connect heater di-
rectly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
Installation Items Needed
Before installing fireplace, make sure you
have the items listed below:
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• manual shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with gas con-
nector (if allowed by local codes) (not
provided)
* An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the A.G.A. design-certified manual
shutoff valve from your dealer.
For propane/LP connection only, the in-
staller must supply an external regulator.
The external regulator will reduce incoming
gas pressure. You must reduce incoming
gas pressure to between 11 and 14 inches of
water. If you do not reduce incoming gas
pressure, heater regulator damage could
occur. Install external regulator with the
vent pointing down as shown in Figure 35.
Pointing the vent down protects it from
freezing rain or sleet.
BDV37(41)N/P AND DDV37(41)N/P
®
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to fireplace. If
pipe is too small, undue loss of
pressure will occur.
Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
fireplace (see Figure 36).
External
Regulator
Vent
Pointing
Down
Figure 35 - External Regulator with Vent
Pointing Down (Propane/LP Only)
A.G.A. Design-Certified
Manual Shutoff Valve with
1/8" NPT Tap*
Approved Flexible
Gas Line
3" Minimum
Figure 36 - Gas Connection
* The A.G.A. design-certified manual shutoff valve may be supplied with the appliance
or you can purchase it from your dealer.
18
IMPORTANT: Install main gas valve
(manual shutoff valve) in an accessible lo-
cation. The main gas valve is for turning on
or shutting off the gas to the appliance.
Check your building codes for any special
requirements for locating manual shutoff
valve to fireplaces.
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged fireplace valves.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Propane/LP
We recommend that you install a sediment
Supply Tank
trap/drip leg in supply line as shown in
Figure 36. Locate sediment trap/drip leg
where it is within reach for cleaning. Install
in piping system between fuel supply and
heater. Locate sediment trap/drip leg where
trapped matter is not likely to freeze. A
sediment trap traps moisture and contami-
nants. This keeps them from going into
fireplace gas controls. If sediment trap/drip
leg is not installed or is installed wrong,
fireplace may not run properly.
Natural - From Gas
Meter (5" W.C. to 10.5"
W.C. Pressure )
Propane/LP - From
External Regulator (11"
W.C. to 14" W.C.
Pressure)
Cap
Pipe Nipple
Tee Joint
Sediment Trap/Drip Leg
104493