Samsung AJ100RCJ5EG Installation Manual page 13

Table of Contents

Advertisement

Specification for circuit breaker and power supply cord
• Power supply cord is not supplied with air conditioner.
• Select the power supply cord in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
Model
Outdoor Unit
Indoor Unit
AJ100RCJ5EG
5 Room
NOTE
1 Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F , IEC:60245 IEC 66 / CENELEC: H07RN-F )
2 Select power supply cord based on MCA.
3 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
4 MCA represents maximum input current.
5 MFA represents capacity which may accept MCA.
Abbreviations
MCA : Min. Circuit Amps. (A)
MFA : Max. Fuse Amps. (A)Tightening power terminal
Outdoor Units
Rated
Hz
Volts
50
1phase, 220-240
Maximum Input Current[A]
Outdoor
Indoor(Max.)
23.0
1.5
Screw
Tighten Torque(kgf.cm)
M4
12.0~18.0
Power Supply
Total
MCA
MFA
24.5
24.50
28.75
Position
1(L),2(L),L,N,F1,F2
English
13