• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future reference.

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AJ100TXJ5KG

  • Page 1 Air conditioner Installation manual AJ100TXJ5KG • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference.
  • Page 2: Table Of Contents

    Step 16 Optional: Power improvement mode Extra procedures Pumping down refrigerant Relocating the indoor and outdoor units Using the stop valve Appendix Troubleshooting For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g. REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_corner.html English...
  • Page 3: Safety Information

    Incorrect installation, use, or maintenance of this appliance can result in death, serious injury, or property damage. Keep these instructions with this appliance. This manual is subject to change. For the latest version, visit www. samsung.com. Notices and notes To make you aware of safety messages and highlighted information, we use the following notices and notes...
  • Page 4 • This manual explains how to install an indoor unit life cycle, the air conditioner must be disposed of in with a split system with two SAMSUNG units. The use authorized centres or returned to the retailer so that of other types of units with different control systems it can be disposed of correctly and safely.
  • Page 5 Installing the unit • Do not cut or burn the refrigerant container or pipings. • Use clean parts such as manifold gauge, vacuum WARNING pump, and charging hose for the refrigerant. • Installation must be carried out by qualified IMPORTANT: When installing the unit, always personnel for handling the refrigerant.
  • Page 6 It is recommended to locate the outlet in a high • Replace components only with parts specified by position. Place the cords so that they are not Samsung. Other parts may result in the ignition of tangled. refrigerant in the atmosphere from a leak.
  • Page 7 Leakage detection methods Recovery • The leakage detector shall be calibrated in a • When removing refrigerant from the system for refrigerant-free area. servicing or decommissioning, it is recommended to remove the entire refrigerant. • Make sure that the detector is not a potential source of ignition.
  • Page 8: Installation Procedure

    Installation Procedure Installation Procedure Power supply line, fuse or circuit Step 1 Choosing the installation location breaker Installation location requirements WARNING • Always make sure that the power supply is compliant • The outdoor unit shall be installed in an open space with current safety standards.
  • Page 9 Sea breeze Stereo Computer etc Outdoor Unit 200 mm Air Guide Duct (This product is not provided by Samsung) CAUTION • Install the unit at a height where its base can be • Depending on the condition of power supply, firmly fixed in place.
  • Page 10 Installation Procedure Minimum clearances for the outdoor unit When installing more than 1 outdoor unit (Unit: mm) When installing 1 outdoor unit 1500 3000 3000 (Unit: mm) or more or more or more or more or more or more or more 2000 or 600 or more...
  • Page 11: Step 2 Checking And Preparing Accessories And Tools

    Step 2 Checking and preparing Step 3 Fixing the outdoor unit in place accessories and tools Install the outdoor unit on a rigid and stable base to 3-wire 2-wire prevent disturbance from any noise caused by vibration. Power Cable (option) Assembly Cable (option) When installing the unit at a height or in a location exposed to strong winds, fix the unit securely to a...
  • Page 12: Step 4 Connecting The Power Cables, Communication Cable, And Controllers

    Installation Procedure Optional: Fixing the outdoor unit to a wall with Step 4 Connecting the power cables, a rack communication cable, and controllers You must connect the following three electrical cables to the outdoor unit: Designed to cut off residual vibration from •...
  • Page 13 Conncting the cables to the outdoor unit A-unit B-unit C-unit D-unit E-unit Indoor unit 1(L) 2(N) F1 1(L) 2(N) F1 1(L) 2(N) F1 1(L) 2(N) F1 1(L) 2(N) F1 Assembly cable F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 Earth Earth Earth...
  • Page 14 Power Supply Model Rated Outdoor Indoor(Max.) Total Outdoor Unit Indoor Unit Volts AJ100TXJ5KG 5 Room 1phase, 220-240 23.0 25.0 25.00 28.75 NOTE 1 Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.
  • Page 15 • Make sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may occur and cause fire and if the terminal is connected too firmly, terminal may get damaged. Transmitter installation(option) • AJ100TXJ5KG PCB MAIN - OUT Do not connect the power and communication...
  • Page 16 Installation Procedure Outdoor-to-indoor power terminal specifications • Connect the cables to the terminal board using the compressed ring terminal. • Cover a solderless ring terminal and a connector part of the power cable and then connect it. Silver solder Norminal Norminal dimensions dimensions...
  • Page 17: Step 5 Optional: Extending The Power Cable

    Outdoor-to-indoor power and communication Step 5 Optional: Extending the power cables specifications cable 1 Prepare the following tools. Indoor power supply Power supply Max/Min (V) Indoor power cable Tools Spec Shape ±10% Crimping pliers MH-14 Communication cable 0.75 to 1.5 mm², 2 wires Connection 20xØ6.5 sleeve (mm)
  • Page 18 Installation Procedure 3 Insert both sides of core wire of the power cable into 6 Apply heat to the contraction tube to contract it. the connection sleeve. Method 2 Method 1 • Method 1: Push the core wire into the sleeve from Contraction tube Contraction tube both sides.
  • Page 19: Step 6 Connecting The Refrigerant Pipe

    A : Minimum required floor area NOTE • IMPORTANT: it’s mandatory to consider either the • AJ100TXJ5KG Outdoor unit cannot be connected to table above or taking into consideration the local law the following indoor unit combination. regarding the minimum living space of the premises.
  • Page 20: Step 7 Optional: Cutting And Flaring The Pipes

    Installation Procedure 3 To prevent any gas from leaking out, remove all burrs CAUTION at the cut edge of the pipe, using a reamer. • 3 m as minimum pipe length: It will reduce noise and 4 Slide a flare nut on to the pipe and modify the flare. vibration.
  • Page 21: Step 8 Connecting Up And Removing Air In The Circuit

    Otherwise, the indoor unit may freeze. • While removing burrs, put the pipe face down to AJ100TXJ5KG make sure that the burrs do not get in to the pipe. • If the valve diameter of indoor and outdoor unit are different, please use Tube-connector.
  • Page 22: Step 9 Performing The Gas Leak Test

    Installation Procedure 5 Set spindle of both liquid side and gas side of stop CAUTION valve to the open position. • Make the electrical connection and leave the system 6 Mount the valve stem nuts and the service port cap into “stand by mode”.
  • Page 23 Important information regulation regarding the refrigerant used In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-32, it is This product contains fluorinated greenhouse gases. Do the responsibility of the installer to pressurize the whole not vent gases into the atmosphere.
  • Page 24: Step 10 Adding Refrigerant (R-32)

    Total connecting Adding Model GWP = 675 pipe length (L) refrigerant Chargeless AJ100TXJ5KG (LT-30m)x10g Outdoor Unit CAUTION • The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).
  • Page 25: Step 11 Connecting The Drain Hose To The Outdoor Unit

    Step 11 Connecting the drain hose to Steel core Carbon plastic Terminal M4 the outdoor unit PVC-insulated To grounding screw green/yellow When heating, ice may accumulate. During the process wire of defrosting, check if condensation draining is 50cm adequate. For adequate draining, do the following : 30cm 1 Insert the drain plug into the drain hole on the underside of the outdoor unit.
  • Page 26: Step 13 Setting An Indoor Unit Address And Installation Option

    Installation Procedure Step 13 Setting an indoor unit address • K4 View mode Display changes and installation option Display Push Push Display Explanation Explanation Setting the indoor unit addresses manually Present Discharge Compressor temperature Frequency 1 Review all the following elements in the installation: •...
  • Page 27 Setting the outdoor option Example) • Press and hold K2 to enter the option setting. (Only available when the operation is stopped) If you enter the option setting, display will show the following. • If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change the function for the selected option.
  • Page 28 Installation Procedure Setting Option <AR*****AA**> <AR*****CA**> Entering mode for setting option Option setting mode Mode button High Temp button Fast button Low Temp button Wind-Free button <AR*****YA**> <AR*****ZA**> Mode button Fast button High Temp button Eco button Low Temp button Mode button High Temp button High Fan button...
  • Page 29 Setting Option 1 Remove batteries from the remote controller 2 Insert batteries and enter the option setting mode while pressing button and button. 3 Each time you press button, 7-seg on left side is increased by “1” and each time you press button, 7-seg on right side is increased by “1”...
  • Page 30 Installation Procedure Operation Indication Step 4 Press button to be changed to DRY mode in the ON status. 1 Press button to enter SEG6. 2 Press button to enter SEG8. Step 5 Press button to be changed to FAN mode in the ON status. 1 Press button to enter SEG9 value.
  • Page 31 Operation Indication Step 11 Press button to be changed to HEAT mode in the OFF status 1 Press button to enter SEG23 value. 2 Press button to enter SEG24 value. Step 12 Press button to check whether the option code you entered is correct or not. Press operation button to enter option.
  • Page 32 Installation Procedure 1 Turn on the outdoor unit, and then check whether the display 1/2 indications are displayed “E199” code. ” and display 2 shows the connected indoor number. • If different display code is shown, see Troubleshooting on page 39 and take corrective actions. 2 Push once the K1 button.
  • Page 33 Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 100-digit of indoor 10-digit of indoor A single digit of Explanation Page Mode Setting main address unit address unit indoor unit Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details No Main address Indication...
  • Page 34 Installation Procedure Setting an indoor unit installation option (suitable for the condition of each installation location) 1 Check whether power is supplied or not. Indoor Unit When the indoor unit is not plugged in, there 1(L) should be additional power supply in the 2(N) indoor unit.
  • Page 35: Step 14 Cool And Heat Modes Operation Test

    Step 14 Cool and Heat modes Step 15 Optional: Setting to Cool or operation test Heat only mode After installing the outdoor and indoor units, test the This function enables the indoor units connected to the Cool and Heat modes. outdoor unit to operate in a specific mode.
  • Page 36: Step 16 Optional: Power Improvement Mode

    Installation Procedure Step 16 Optional: Power improvement mode The power improvement mode has the following power reduction effects. • Reduced power at Thermo off When the air conditioner operates in Cool, Dry and Auto mode, if Thermo off is reached during cooling, the fan and display of the indoor unit are turned off after 5 minutes.
  • Page 37: Extra Procedures

    Extra Procedures Pumping down refrigerant Relocating the indoor and outdoor units WARNING 1 Pump down refrigerant. See Pumping down • After installing the product, be sure to perform leak refrigerant on page 37. tests on the piping connections. After pumping down 2 Remove the power cord.
  • Page 38: Using The Stop Valve

    Extra Procedures Using the stop valve Closing the stop valve 1 Remove the cap. 2 Turn the stop valve clockwise by using a hexagonal Opening the stop valve wrench. 3 Tighten the axis until the valve reached the sealing 1 Open the cap and turn the stop valve anticlockwise point.
  • Page 39: Appendix

    Appendix Troubleshooting The table below list the self-diagnostic routines. For some of PCB MAIN - OUT error, you must contact an authorized service center. If an error occurs during the operation, it is displayed on the outdoor unit PCB MAIN-OUT. 88 SEG DISPLAY Error Code Explanation...
  • Page 40 Appendix Error Code Explanation Remark E416 COMPRESSOR OPERATION STOP DUE TO DISCHARGE TEMPERATURE PROTECTION CONTROL E422 HIGH PRESSURE BLOCKAGE CONTROL E440 HEATING MODE RESTRICTION DUE TO HIGH AIR TEMPERATURE E441 COOLING MODE RESTRICTION DUE TO LOW AIR TEMPERATURE E458 FAN MOTOR ERROR E461 OPERATION FAILURE OF COMPRESSOR E462...
  • Page 41 MEMO English...
  • Page 42 SAMSUNG ELECTRONICS CO., LTD. 107, Hanamsandan 6beon-ro, Gwangsan-gu, Gwangju-si, Korea 62218 Samsung Electronics Service Department PO Box 12987, Blackrock, Co. Dublin. Ireland Blackbushe Business Park, Yateley, GU46 6GG. UK...