AUTOMATIC RECHARGE

The OM34K and OM40K use an internal water meter that
counts the gallons used . When the recharge setpoint (gallons
of water treated) is reached, the unit will recharge . The setpoint
depends on the capacity setting used (HE or HC) and the
hardness of the water . See page 20 for rated capacities and
system performance .

MANUAL REGENERATION

Delayed Regeneration
Press and release
to program a delayed regeneration . The
system will regenerate at the next Time of Regeneration
(2:00 AM) . Repeat procedure to disable the Delayed Regen .
Regen dot blinks when delayed regeneration is on .
Immediate Regeneration
Press and hold the
for 3 seconds to initiate an immediate
regeneration . The control cycles to backwash . The control
will proceed through a complete regeneration . A cascading
symbol (- -) will be displayed until regeneration is complete .
The symbol (- -) is not displayed during a quick cycling of the
control .
Figure 16

QUICK CYCLING THE CONTROL

Quick Cycling
Press and hold the
for 3 seconds to initiate an immediate
regeneration . The control will cycle to the backwash cycle .
1 . Press and release the
2 . Simultaneously press then release
control to the next cycle .
NOTE: The time may be displayed for 5 seconds.
3 . Press and release the
Continued pressing of
"- -" and "C#" .
4 . Repeat steps 2 and 3 to cycle through each position .
Quick Cycle to Service Position
Simultaneously press
and
any regeneration cycle . The control will skip the remaining
regeneration cycles and return to the service position . The
Time of Day will be displayed when the control reaches the
service position .
to display "C 1"
and
to move the
to display "- -" or the "C#" .
will switch the display between
and hold for 3 seconds during
Figure 17

CYCLE DEFAULTS TABLE

OM34K Recharge Cycles:
Table 1
Length of Cycle
Cycle
Cycle
HE
Description
Setting
1
Backwash 1
10 min
2
Brine Draw
54 min
Slow Rinse
3
Re-
3 min
Pressurize
4
Fast Rinse 1
4 min
5
Backwash 2
1 min
6
Fast Rinse 2
1 min
7
Refill
3 .5 min
*The camshaft does not move between Brine Draw and Slow Rinse.
Slow Rinse begins when the brine in the salt tank runs out and the
check valve closes .
OM40K Recharge Cycles:
Table 1
Length of Cycle
Cycle
Cycle
HE
Description
Setting
1
Backwash 1
10 min
2
Brine Draw
51 min
Slow Rinse
3
Re-
3 min
Pressurize
4
Fast Rinse 1
4 min
5
Backwash 2
1 min
6
Fast Rinse 2
1 min
7
Refill
4 .1min
*The camshaft does not move between Brine Draw and Slow Rinse.
Slow Rinse begins when the brine in the salt tank runs out and the
check valve closes .
Time remaining to
end of cycle
HC
HE
HC
Setting
Setting
Setting
10 min
76 .5 min
117 .5
min
107 .5
82 min
66 .5 min
min
3 min
12 .5 min
25 .5 min
4 min
9 .5 min
22 .5 min
1 min
5 .5 min
18 .5 min
1 min
4 .5 min
17 .5 min
16 .5 min
3 .5 min
16 .5 min
Time remaining to
end of cycle
HC
HE
HC
Setting
Setting
Setting
10 min
74 .1 min
118 .1 min
79 min
64 .1 min
108 .1 min
3 min
13 .1 min
29 .1 min
4 min
10 .1 min
26 .1 min
1 min
6 .1 min
22 .1 min
1 min
5 .1 min
21 .1 min
20 .1 min
4 .1 min
20 .1 min
11