[ VIII Test Run Mode ]
[4] Refrigerant
Unit type
Refrigerant type
Refrigerant charge
[5] Symptoms that do not Signify Problems
Symptom
The display shown right will appear
on the unit remote controller for
about 5 minutes when the main
power source is turned on.
[6] Standard operating characteristics (Reference data)
Reference data
heat source
Temperature
Inlet heat source temperature
Outlet heat source temperature
Inlet hot water temperature
Outlet hot water temperature
Pressure
Compressor
HWE1312A
CRHV-P600YA-HPB
R410A
4.5kg × 2
Remote controller display
"PLEASE WAIT" ("HO")
blinking display
flow
Discharge refrigerant
Suction refrigerant
Shell temperature
High pressure
Low pressure
Frequency
The system is under starting up.
Operate the remote controller after the blinking of
"PLEASE WAIT" ("HO") is disappeared.
-
Counter
°C
65
°C
0
°C
17
°C
0
°C
-3
°C
30
°C
35
MPa
2.05
MPa
0.57
Hz
82
- 108 -
Cause
Parallel
65
-3
14
0
-3
30
35
2.05
0.51
82
GB