Mns Override; Auxiliary Power; Trouble Reminder; Language - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

Programming

MNS Override

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
System Setup Screen #3
MNS Override feature will become unavailable.

Auxiliary Power

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
System Setup Screen #4
Select the desired output. The following screen will be displayed.
Each output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for powering annunciators while
resettable power is suitable for powering smoke detectors. Each press of the 2 key will cause the display to toggle between Resettable
Yes and Resettable No.
In addition, Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause
the display to toggle between Class A Yes and Class A No.

Trouble Reminder

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
System Setup Screen #4

Language

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4

Charger Enable

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5

4XTMF Supervision

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5

Remote Sync Enable

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5
80
Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the system for
use with the Mass Notification System (ECC-50/100 panel). Each press of the 3 key will toggle the display
between MNS Override No and MNS Override Yes. When MNS Override No is selected, the ECC-50/100
NO
panel does not have permission to override the FACP. When MNS Override Yes is selected, the ECC-50/100
panel will override the FACP, taking control of its NACs and control modules during a mass notification
event. Refer to the ECC-50/100 Manual for more information. When the Canadian Option is set to On, the
Two Special Application 24 VDC power outputs are available at TB11 on the main circuit board. Pressing 3
while viewing System Setup Screen #4 displays the following:
24HR
1=AUX 1
2=AUX 2
1=CLASS A
2=RESETTABLE
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for alarms and
troubles, after the panel has been silenced. Refer to "Trouble Reminder" on page 71, for a detailed descrip-
24HR
tion of this feature. Pressing 2 while viewing System Setup Screen #4 will cause the display to toggle to
Trouble Rem 4 or Trouble Rem 24, which enables this feature for resound at either 4 or 24 hours, respec-
tively. Each press of the 1 key will cause the display to toggle between Trouble Rem 4 or Trouble Rem 24.
Refer to the table on page 49 for permissible settings.
The language option is used to change the text on the panel display to either English or French. Pressing the
3 key will cause the display to offer a choice of 1=English and 2=French.
24HR
If using an external battery charger, the FACP battery charger must first be disabled. Pressing 1 while view-
YES
ing System Setup Screen #5 will cause the display to toggle to Charger Enab No, which will allow the use
NO
of an external battery charger. Each press of the 1 key will cause the display to toggle between Charger
YES
Enab Yes and Charger Enab No.
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
YES
Pressing 2 while viewing System Setup Screen #5 will cause the display to toggle to 4XTM Supv Enab. Yes,
NO
which means there is a 4XTMF installed. Each press of the 1 key will cause the display to toggle between
YES
4XTM Supv Enab. No and 4XTM Supv Enab. Yes. Refer to the table on page 49 for permissible settings.
Synchronization is a feature that controls the activation of notification appliances in such a way that all
devices will turn on and off at exactly the same time. Refer to Section 2.5, "Remote Synchronization Out-
YES
NO
put", on page 28 for more information. To enable remote synchronization, press the 3 key while viewing
YES
System Setup Screen #5. Each press of the key will toggle the screen between Rem Sync Enab Yes and Rem
Sync Enab No.
AUX POWER
AUX 1
YES
YES
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018