7-2. Room Temperature Sensor Setting
The room temperature sensors are built into the indoor unit and the wireless remote controller. Either of these room
temperature sensors can operate.
The system is shipped from the factory set to the indoor unit sensor. To switch to the remote control sensor, press the
sensor switching button located inside the remote control cover and check that A/C SENSOR on the LCD display panel
goes out.
NOTE
If the sensor switch is set to the remote controller side,
but no room temperature data is sent to the main unit
for 10 minutes, the sensor is automatically switched to
the indoor unit side. As much as possible, install the
remote controller facing the unit.
7-3. Address Switches
If you are installing more than 1 indoor unit (up to 6) in the same room, it is necessary for you to assign each unit its
own address so they each can be operated by their remote controller.
Up to 6 indoor units can be controlled separately through the address switches. The operating control has the reception
address switch and the remote controller has the transmission address switch. This function is utilized by matching the
transmission and reception address switches.
Remote control
ADR
address display
Address switch
* Any address
switch position
positions
available
7-4. Setting the Model Code
Flap display selector switch
Make the slide switch settings in the battery compartment box of the remote controller depending on the type of
indoor unit in which the wireless receiving unit is used.
Operation mode switch
In this Single Split System Air Conditioner set the switch to "A".
* The switch is factory set to "S" / "A".
* Always press the reset button after switching the setting.
S
K
N
A
H
C
2
1
Fig. 1-87
ADR
ADR
1 2 3
1 2 3
4 5 6
4 5 6
Operation
1
mode switch
U
, 1
Flap display
2
Heat pump with
selector switch
Auto mode
Sensor button
S
K
N
S
K
N
T
1
y t
p
e
s
K1 type
A
H
C
A
H
C
Heat pump without
Auto mode
1-101
1. Specifications
Fig. 1-86
ADR
1 2 3
4 5 6
S
K
N
F
1
y t
p
e
A
H
C
Cooling only