5.2

Creation of Test Program

1. Input/output assignment
Inputs/outputs are assigned as shown in the following table:
Limit switch
Manual switch
"Pulse train" signal or "forward rotation pulse train" signal (output specified for pulse output
destination)
"Direction" signal or "reverse rotation pulse train" signal (output specified for rotation
direction signal)
2. Setting of related devices
The following related devices depend on the pulse output destination device that is set for the positioning
instruction. If the pulse output destination device is changed, it is necessary to change the related devices.
Items related to speed
Maximum speed
Bias speed
Acceleration time
Deceleration time
Forward/reverse rotation speed
Forward limit, reverse limit, and immediate stop of pulse output
Forward limit
Reverse limit
Status check items
Positioning (Y000)
"Instruction execution abnormal
end" flag
Current value register (Y000)
B - 96
Downloaded from
ManualsNet.com
/FX
/FX
PLC User's Manual - Positioning Control Edition
3U
3UC
Forward rotation limit 1
Reverse rotation limit 1
Forward rotation (JOG+)
Reverse rotation (JOG-)
Setting item
100,000Hz
0Hz
100ms
100ms
30,000Hz
If X010 is turned off (if the NC contact is
turned on), the limit switch will be
activated.
If X011 is turned off (if the NC contact is
turned on), the limit switch will be
activated.
Use this device to check whether the
positioning instruction is being
activated.
Use this device to check whether or not
the forward/reverse rotation limit switch
turns ON.
Stores the current value of the
positioning operation in Y000.
search engine
Signal
For setting items of the related devices, refer to Subsection 4.5.1.
Description of setting
5 Operation Test
5.2 Creation of Test Program
Input/output number
NC contact
X010
NC contact
X011
NO contact
X012
NO contact
X013
Y000
Y004
Related
Setting value or
device
condition
D8344,D8343
K100000 Initial value
(32-bit)
D8342
K0 Initial value
D8348
K100 Initial value
D8349
K100 Initial value
-
K30000
M8343
ON: If X010 = OFF
M8344
ON: If X011 = OFF
Turns on when the
M8348
positioning instruction is
activated.
Turns on when the limit
switch is activated
M8329
during a positioning
operation.
D8341,D8340
Varies when a positioning
(32-bit)
instruction turns ON.
-