Exhaust Requirements
Following are important instructions and information concerning the exhaust requirements for
your dryer.
Caution!
To reduce the risk of fire, electric shock, or injury to person, read the IMPORTANT SAFETY
INSTRUCTIONS before operating this appliance. To reduce the risk of fire, combustion,
or accumulation of combustible gases, DO NOT exhaust dryer air into an enclosed and
unventilated area, such as an attic, wall, ceiling, crawl space, chimney, gas vent, or
concealed space of a building. To reduce the risk of fire, DO NOT exhaust the dryer with
plastic or thin foil ducting
Weather Hood Type
Recommended
Use Only for Short
Run Installations
Note!
Deduct 6 feet (1.8 m) for each additional elbow. It is not recommended to use more than (4)
90° elbows.
44
Maximum length of 4˝
Number of
(10.2 cm) diameter rigid
90° Elbows
metal duct
0
65 feet (19.8 m)
1
55 feet (16.8 m)
2
47 feet (14.3 m)
3
36 feet (11.0 m)
4
28 feet (8.5 m)
55 feet (16.8 m)
0
47 feet (14.3 m)
1
41 feet (12.5 m)
2
30 feet (9.1 m)
3
22 feet (6.7 m)
4
Customer Care Center
1-800-898-1879
www.askousa.com
Maximum length of
4˝ (10.2 cm) diameter
flexible metal duct
45 feet (13.7 m)
35 feet (10.7 m)
30 feet (9.1 m)
25 feet (7.6 m)
20 feet (6.1 m)
35 feet (10.7 m)
27 feet (8.2 m)
21 feet (6.4 m)
17 feet (5.2 m)
15 feet (4.5 m)