Installation Instructions
Step 3. Connection of gas supply
(Gas dryer only). In addition to the following,
please refer to manual section on Gas
Requirements and Instructions.
1
2
5
3
4
1. New stainless steel flexible connector.
Use this type of connector only if allowed
by local codes. Use design AGA certified
connector (CGA in Canada).
2. 1/8" NPT pipe plug (for checking inlet
gas pressure)
3. Equipment shut-off valve, Installed within
6' (1.8 m) of dryer
4. Iron Pipe: Shorter than 20' (6.1 m), use
3/8" pipe. Longer than 20' (6.1 m), use
1/2" pipe.
5. 3/8" N.P.T. gas connection
Note!
Make sure the burner nozzle is proper for
the type of gas you are provided with.
For instance, using LPG with LNG nozzle
will result in death, fire or explosion. Or using
LNG with LPG nozzle will not ignite burner.
If needed, nozzle conversion should be
done by a qualified service technician. Mark
or label the dryer with the current type of
nozzle on the dryer.
1. Confirm that the type of gas available in
your laundry room is appropriate for the
dryer. The dryer is prepared for Natural
Gas with a 3/8" NPT gas connection.
2. Remove the shipping cap from the gas
connection at the back of the dryer.
Make sure that you don't damage the
threads of the gas connection pipe when
you remove the shipping cap.
3. Connect the dryer to your laundry room's
gas supply using a new flexible stainless
steel connector (as noted below, only use
a new stainless steel flexible connector if
allowed by your local codes) using Pipe
Joint Compound that is insoluble in gas
for all gas line connection points.
*Do not use Teflon tape
4. Securely tighten all connections between
the dryer and your laundry room's gas
supply. Turn on your laundry room's gas
supply and check all pipe connections
(both internal and external) for gas leaks
with a non-corrosive leak detection fluid.
Refer to Part 7(page 20)
5. For LP (Liquefied Petroleum) gas
connection, refer to this manual's
section entitled Gas Requirements and
Instructions.
Note!
Burner input requirements
If your house is located at the elevation up to
10,000 feet, the burner adjustment setting is
not necessary. The A.G.A. certifies this dryer
will not have any problem with the B.T.U
rating at this altitude.
If your house is above 10,000 feet, you
are required to adjust a four percent(4%)
reduction of the burner B.T.U rating indicated
on the model/serial rating plate.