U-Line Wine Captain 1000 Series User Manual & Service Manual page 52

24" single zone
Hide thumbs Also See for Wine Captain 1000 Series:
Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
To ensure the windings are not shorted, check the S
and R to ground.
Refrigerant
Voltage
Frequency
Run Cap
Start Winding
Run Winding
LRA
FLA
Starting Device
Overload
* All resistance readings are ±10%
EMX20CLC
R600a
115 - 127 VAC
60 Hz
12μF/165 VAC
6.7 Ohm at 77°F
12.6 Ohm at 77°F
3.7 A
0.5 A
8EA14C
4TM142RFBYY-53
u-line.com
Compressor Specifications 1