13.3 Error History
Boiler control is equipped with error memory which, records
last 16 errors. In addition to storing error codes, the following
data is also saved:
• Number of times that the error occurred: (n:xx).
• Boiler operating mode selected (St:xx).
• The supply temperature (t1:xx) and the return
temperature (t2:xx) when the error occurred.
To view the error history, enter access code 0012.
Readout
13.4 Error History
buttons simultaneously and then (+)
• Press two
button until the
• Select the installers menu using
appears on the display.
• Use (-) or (+) button to input installer code 0012.
• Press
button. "Er:xx" appears on the display.
• The fault list can be displayed by pressing (-) or (+)
button.
• Confirm using
"xx" flashing = Last error which occurred, for example
"2".
• Use (-) or (+) buttons to scroll through faults.
• Press
button to display details of faults or
shutdowns.
• Press (-) or (+) buttons to view the following
information:
n:1 = Number of times that the error occurred.
hr = The number of operating hours.
St = State.
Su = Sub-status.
t1 = Supply temperature ºF/ºC.
t2 = Return temperature ºF/ºC. t3 = DHW tank
temperature ºF/ºC.
t4 = Outdoor temperature ºF/ºC (Only with an outdoor
temperature sensor).
t5 = Solar panel temperature ºF/ºC. t6 = Flue gas
temperature ºF/ºC.
Sp = Internal set point ºF/ºC.
fl = Ionization current (μA).
nf = Fan speed in rpm.
Pr = Water pressure psi/bar.
Po= Supplied relative heat output (%).
button to interrupt display cycle. "Er:xx" is
• Press
displayed with "xx" flashing = Last error which occurred.
• Use (-) or (+) button to scroll through faults.
• Press
button to show fault list.
• Press
button 2 times to exit error history.
13 - TROUBLE SHOOTING
symbol flashes on the menu bar.
button. "CODE"
button. "Er:xx" is displayed with
2x
73
PN 240011662 Rev. K [01/31/2020]