FIGURE 6-24 Secure Clamp around Flue Adapter
FIGURE 6-25 Maximum Distance Between Supports
Horizontal
6 - COMBUSTION AIR AND VENT PIPING
Vertical
5.
Connect 90° elbows to horizontal common vent pipe for
each boiler in cascade system
6.
Connect flue damper to 90° elbow for each boiler in
cascade system.
7.
Connect boiler flue adapter to flue damper for each boiler
in on multiple venting applications. Ensure flue adapters
allow for 3° or 2 in. per 3 ft. slope of horizontal collectors
back towards condensate collector.
8.
Connect intake air screen to flue adapter for each boiler in
cascade system. Combustion air shall come from indoors
only.
9.
Connect cascade vent system to flue connection on top of
boilers.
10.
Connect end cap and condensate trap to horizontal
common vent pipe.
11.
Secure flue adapters using approved clamps to wall.
Ensure clamps are connected minimum of 10 in. from top
of boiler. See Figure 6-24.
12.
Secure approved clamp around flue adapter. Ensure clamp
is locked in to proper position. See Figure 6-24.
A. Position 1 - Clamping around bell end of adapter.
B. Position 2 - Clamping around flue pipe adapter.
13.
Maximum distance between supports for horizontal pipes
3 ft 4 in. Maximum distance between supports for vertical
pipes 6 ft 7 in. See Figure 6-25.
14.
Fully tighten horizontal common vent pipe supports.
33
PN 240011662 Rev. K [01/31/2020]