Heating System And Refrigeration; Manifold Installation (Supplied) - UTICA BOILERS UCS 380 Installation, Operation And Maintenance Manual

Condensing gas fired boiler
Table of Contents

Advertisement

WARNING
!
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
• Route pressure relief valve discharge piping to the floor.
Follow local code with respect to necessary distance to the
floor. See Figure 5-3.
• Verify all valves are closed.
• Connect supplied condensate trap to a drain. Verify there is
continuous slope towards the drain, avoid level horizontal
sections of tubing.

5.7 Heating System And Refrigeration

Boiler when used in connection with refrigeration system,
must be installed so chilled medium is piped in parallel with
the boiler with appropriate valves to prevent chilled medium
from entering the boiler.
Boiler piping system of hot water boiler connected to heating
coils located in air handling units where they may be exposed
to refrigerated air circulation must be equipped with flow
control valves or other automatic means to prevent gravity
circulation of the boiler water during the cooling cycle.
5.8 Labor Savor Manifold Installation (supplied) See
Figure 5-3
1.
Boiler is supplied with union connection installed on boiler
piping for connection to manifold.
2.
Configure manifold to suit the application.
Identify BOILER supply and return when
Note
installing manifold.
3.
Tighten manifold in place. Check for leaks.
5 - HYDRONIC PIPING
13
PN 240011662 Rev. K [01/31/2020]

Advertisement

Table of Contents
loading

Table of Contents