Other Programming
S
E

4.1 Program Zones and Partitions

Now that you have enrolled the wireless devices, you should complete all zone
programming on the system. Although the exact programming required varies
depending on which control panel the LCD5501Z32-433 is connected to, you
should check that the following programming areas are completed correctly for
each wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming
sections [201]-[209]).
• Program the definition for each zone (programming sections [001]-[004]).
NOTE: WLS906 wireless smoke detectors must be assigned to zones defined as
Delay 24-hr fire (wireless) [87] or Standard 24-hr fire (wireless) [88] for proper
supervision.
• Enable the wireless zone attribute for each wireless zone (PC580, PC1555,
PC5008, PC5010 v2.0 and up, PC5015 v2.2 and up only) (programming sections
[101]-[132]).
See your system Installation Manual , for more information on each of the above
programming sections.

4.2 Enable Receiver Supervision

The control panel will automatically supervise the receiver via the Keybus one-
minute after at least one device has been enrolled on the module. The system will
generate a General System Supervisory trouble if the module is removed from the
Keybus. If you need to remove the LCD5501Z32-433 from an existing system, you
will have to disable supervision of the PC5132.

4.3 Enable Supervision of Wireless Zones

NOTE (for PC5010 v1.x control panels only): For UL Listed installation, Double
EOL resistors must be enabled in the PC5010 for the wireless zones to be super-
vised. If normally Closed or Single EOL resistors are selected the PC5010 will not
be able to supervise the wireless devices. If a wireless device stops sending a
supervisory signal (the unit stops functioning) the panel will not indicate a super-
visory trouble condition unless Double EOL resistors are used. In addition, all
hardwire zones must be wired for Double EOL resistors. For more information,
refer to your PC5010 v1.x Installation Manual.
NOTE (PC5010 v2.0 and higher, PC5015 v2.2 and higher, PC5008, PC1555, PC580
only): For wireless supervision to work, you must enable the wireless zone attribute
on all wireless zones (sections [101] to [132], option [8] ON).
NOTE: The RF Jam Detect zone must have the supervision option disabled.
Wireless Supervisory Window
Each wireless zone (WLS904, WLS904P, WLS906, WLS907, WLS912, WLS914,
WLS925L) will send a supervisory signal every 64 minutes. If the receiver does not
receive a signal within the time programmed for the Wireless Supervisory Window,
it will generate a supervisory fault.