Superior Fireplaces VRT4032ZEP Manual page 16

Unvented (vent-free) radiant and louvered faced fireplace system with logs and thermostat blower
Table of Contents

Advertisement

fi replace base area while replacing log
base assembly. Make sure the entire
fl exible gas line is in fi replace base area.
Reattach log base assembly to fi replace
with screws removed in step 2, Page 15.
CAUTION: Do not pick up
log base assembly by burner.
This could damage burner. Only
handle base by grates.
Figure 19 - Removing Log Base
Assembly From Fireplace
To Fireplace Gas
Equipment Shutoff
Regulator
Valve Provided by
Installer
Flexible Gas Line
from Fireplace Gas
Regulator
Figure 20 - Attaching Flexible Gas Lines
Together
NOTICE: Most building codes
do not permit concealed gas
connections. A fl exible gas line
is provided to allow accessibility
from the fi replace (see Figure 20).
The fl exible gas supply line con-
nection to the equipment shutoff
valve should be accessible.
16
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
open fl ame to check for a leak.
Apply a noncorrosive leak detec-
tion fl uid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
fi replace. See guidelines under
Connecting Fireplace to Gas
Supply, Page 15.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fi replace with its main gas
valve (control valve) and equipment shut-
off valve from gas supply piping system.
Propane/LP
Pressures in excess of 1/2 psig (3.5 kPa)
To External
will damage fi replace regulator.
Regulator
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
Natural Gas
opening propane/LP supply tank valve
To Gas Meter
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas, or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fl uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment
shutoff valve to gas supply. Check recon-
nected fi ttings for leaks.
SuperiorFireplaces.us.com
WARNING: Never use an
900719-00C