Vertical Vent Tables And Figures - Superior Fireplaces DRC6300 Series Installation And Operation Instruction Manual

Hide thumbs Also See for DRC6300 Series:
Table of Contents

Advertisement

Innovative Hearth Products
DRT/DRC6300 Series Direct-Vent Gas Fireplaces
VERTICAL VENT FIGURES/TABLES
NOTES:
• Secure Vent
(rigid vent pipe) is shown in
®
the figures.
• It is very important that the horizontal/
inclined run be maintained in a straight
(no dips), slightly elevated plane. The
recommended incline is approximately
1/4" per foot (20 mm per meter) horizontal,
in a direction away from the fireplace. The
rise per foot run ratios that are smaller are
acceptable all the way down to at or near
level.
• SV8BF (Secure Vent) firestop/spacer must
be used anytime vent pipe passes through a
combustible floor or ceiling. SV8HF (Secure
Vent) firestop/spacer must be used anytime
vent pipe passes through a combustible wall.
• Two 45º elbows may be used in place of one
90º elbow. The same rise to run ratios, as
shown in the venting figures for 90º elbows,
must be followed if 45º elbows are used.
40 feet (12.2 meters)
Ceiling
Firestop/Spacer
(SV8BF)
A Vent Restrictor, as shown in Figure 17 on Page
12, may need to be used in this application
Figure 23—Top Vent—Straight
18
V1
Figure 24—Top Vent—Two 90 Degree Elbows (Corner Framing with Square
Termination (SV8HTS))
Maximum
6 feet (1.8 meters)
Minimum
Figure 25—Top Vent—Three Elbows
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
H
Ceiling
Firestop/Spacer
(SV8BF)
Ceiling
Firestop/Spacer
V 1
(SV8BF)
H
H 1
Table B
V Minimum
H + H 1 Maximum
feet
(meter)
feet
10
(3.1)
2.5
15
(4.65)
3.5
20
(6.2)
4.5
H + H 1 = 20 feet (6.2 m) Max.
V + V 1 + H + H 1 = 40 ft. (12.4 m) Max.
V + V 1 = 11 feet (3.3 meters) Min. for 40 in. units
V + V 1 = 10.5 feet (3.2 meters) Min. for 45 in. units
Table A
H Maximum
feet
(meter)
10
(3.1)
15
(4.65)
20
(6.2)
V + V
+ H = 40 feet (12.4 meters) Max.
1
V + V
= 11 feet (3.3 meters) Minimum for 40 in. units
1
V + V
= 10.5 feet (3.2 meters) Minimum for 45 in. units
1
Example: If 20 feet of (H) horizontal
vent run is needed, then 4-1/2 feet
V
minimum of (V) vertical vent will be
required.
A Vent Restrictor, as shown in
Figure 14 on Page 14, must be used
in this application.
Wall
Firestop/Spacer
(SV8HF)
V
(meter)
(0.762)
(1.06)
(1.37)
Example: If 20 feet of (H+ H
tal vent run is needed, then 4-1/2 feet
minimum of (V) vertical vent will be
required.
Installation
900343-01 01/2018
V Minimum
feet
(meter)
2.5
(0.762)
3.5
(1.07)
4.5
(1.37)
A Vent Restrictor, as
shown in
Figure 14 on Page 14,
must be used in this
application.
) horizon-
1