Access Control; Door Access - Chamberlain CAPXS Installation Manual

Smart video intercom s
Table of Contents

Advertisement

Available languages

Available languages

INTRODUCTION

Door Access

Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access.
WIEGAND
KEYPAD
SUPERVISED
(DOOR STATUS)
DOOR SENSOR
(SUPERVISED)
EOL (End of Line) Resistor
(1k ohm)
OR
DOOR SENSOR
(NON-SUPERVISED)
*PRIMARY RELAY
DOOR STRIKE
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
ACCOUNT SETUP
READER
OR
NOTE: For KPR2000 keypad
wire the pink and black (ground)
wires together.
REQUEST TO EXIT
PROXIMITY
PUSH
SENSOR
BUTTON
OR
REQUEST TO EXIT
GROUND
SUPERVISED
For AC Power:
Install a Siemens
S10K30MOV
(Metal Oxide Varistor) or
equivalent
Power for Door Strike
(Not Provided)
COMMON
+
NORMALLY OPEN
OR
MAGLOCK
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) or
equivalent
NORMALLY CLOSED
COMMON
+
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
POWER
NETWORK/MOUNTING
12 VDC POWER SUPPLY
POSTAL LOCK**
POSTAL LOCK
NORMALLY OPEN (N.O.)
COMMON (COM)
GROUND (BLACK GND)
DATA 0 (GREEN DATA0)
DATA 1 (WHITE DATA1)
REQUEST TO EXIT (REX)
GROUND (GND)
SUPERVISED
NORMALLY OPEN (N.O)
COMMON (COM)
NORMALLY CLOSED (N.C.)
NORMALLY OPEN (N.O.)
COMMON (COM)
AUXILIARY RELAY
Low
Voltage
Power
Supply
Isolation
Relay
NOTE: DO NOT
connect high
voltage power
to the CAPXS
ALARM BYPASS
unit.
COMMON
NORMALLY OPEN
15

ACCESS CONTROL

NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
POWER
ETHERNET CONNECTION
LIGHT
DO NOT INSTALL THE
SYSTEM IN THE FAIL
SECURE MODE UNLESS
LOAD
PERMITTED BY THE LOCAL
LINE
AUTHORITY HAVING
JURISDICTION. Doing so
may cause interference with
OR
the operation of panic
hardware.
* NOTE: MAGLOCK, door strike and
ALARM BYPASS not evaluated by UL.
** NOTE: For more information on how
to wire in a postal lock, refer to the
manual for accessory: CAPXSTKPL.

Advertisement

Table of Contents
loading

Table of Contents