Bluetooth LED Status

Mode
BLE disabled by user
BLE normal operation
and connected
BLE enabled but not
connected
BLE failure

Controller LED Status

Mode
Firmware download
a)
No application
Broken sensor
Short circuit
AutoMac
No Valid Mac
Un Ack Alarm
Normal operation
Communication error Red LED blinks every 200 ms.
a)
While performing setpoint balancing using the VAV mobile application, the LED pattern changes from static
green to red, green, yellow cycles (which indicates the controller is empty).
b) For troubleshooting a permanent red LED, navigate to IRM Program > On Board IO and check the UIO function
block OutCase status. A permanent red LED will be illuminated when the OutCase status is SensorOpen (broken
sensor) or SensorClose (short circuit).
Table 25 Bluetooth LED Status
LED Status
OFF
Green, permanently ON.
Green, 2 blinks in 1 s followed by
2 s pause, and repeat.
Red, permanently ON.
Table 26 Controller LED Status
LED Status
Green blinks every 200 ms.
Red, Green, Yellow blinks every 1 s.
b)
Red permanent ON
.
Green blinks every 2 s.
Yellow permanent ON.
Yellow blinks every 2 s.
Green LED permanent ON.