ABB PCS100 AVC-20 User Manual page 87

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual
Address
Name
16
Frequency
17
Active Event
Code
18
Auto
Increment
Register
26
Product Code
27
SCM Fault
Code
28
PQ sag count
29
PQ sag count
30
PQ sag count
31
PQ sag count
32
PQ sag count
33
PQ sag count
34
PQ sag count
35
PQ sag count
36
PQ sag count
37
PQ surge
count
38
Output
Apparent
Power
39
Output Real
Power
100
Time and
Date
1000
Reset
Command
Access
Type
Read Only
16-bit,
Signed
Read Only
16-bit,
Signed
Read Only
16-bit,
Enum
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
unsigned
Read Only
16-bit
signed
Read Only
16-bit
signed
Read/Write
32-bit
unsigned
Read/Write
16-bit,
Enum
Raw Value & Scaling
Frequency (Hz) = raw value x rated
frequency / 8192
e.g., raw value = 8192
rated frequency = 60Hz
Frequency = 60.0Hz
See Table 9-2Event code 0 indicates there
are no active events (no warning/fault).
Read = Register automatically increments
by 1 every time this is read
7300=AVC
System Configuration Module state (fault
code)
0%-10%
10%-20%
20%-30%
30%-40%
40%-50%
50%-60%
60%-70%
70%-80%
80%-90%
>110%
Per-unit. Base Power
= √3 * Rated Voltage (register 4) * Rated
Current (register 6)
Unix (Epoch) Time – Number of seconds
since 01/01/1970.
Note – If write error, enable with menu 731
Date Write Enable
0 = No Action
1 = Reset
87