8.3.3
Menu 1 System Electrical
1 System Electrical
The menu contains electrical settings for the product
Parameter:
Function:
Access:
Range:
Units:
Factory Setting:
Parameter:
Function:
Access:
Range:
Default:
Setting Up:
Parameter:
Function:
Access:
Range:
Default:
Setting Up:
Note:
Parameter:
Function:
Access:
Range:
Default:
Setting Up:
Parameter:
Function:
Access:
Range:
Default:
Setting Up:
Parameter:
Function:
Access:
Range:
Unit
Default:
10 System Current
Set total rated current of system – Line RMS.
Tech
0.00 to 1751.95
Amps (RMS)
PCS100 AVC-20 rated current
11 Rectifier Voltage
Set typical AC (RMS) input voltage of rectifiers.
Tech
10 V to 1000 V
Model dependent
Preset in the factory
12 Transformer Config
Selects the Injection transformer terminal configuration
Tech
Top Input / Bottom Input
Top Input
Preset in the factory
Top Input = utility supply (input) to top. Bottom Input = utility supply (input) to
bottom. Changing this setting alone does not change the transformer
configuration. Wiring changes are also required.
13 Supply Voltage
Adjusts the PCS100 AVC-20 working voltage
Tech
0.00 V to 1599.95 V
Nameplate rating of PCS100 AVC-20
Set to nominal supply voltage ± 10% (RMS)
14 Supply Frequency
Set the supply voltage frequency.
Tech
40 Hz to 400 Hz
Nameplate rating of PCS100 AVC-20
Set to nominal supply frequency
15 Sag Threshold
Power quality meter sag recording threshold.
Operator
0 % to 399.99%
Percentage of parameter 13 Supply Voltage
90%