Pcs100 Avc-20 Performance Curves; How To Use Performance Curves - ABB PCS100 AVC-20 User Manual

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual
If the utility voltage deviates beyond +/- 20%, the PCS100 AVC-20 will still provide continuous regulation to as
close to nominal voltage as possible, ensuring trouble free operation of the protected equipment.
The adaptive approach to performance enables users to select the unit based on the load or based on the
required output voltage accuracy

2.3 PCS100 AVC-20 Performance Curves

This section explains PCS100 AVC-20 general performance for undervoltage and overvoltage.
PCS100 AVC-20 Output Voltage
120%
115%
110%
105%
100%
95%
90%
85%
80%
70%
75%
2.1.1

How to Use Performance Curves

1.
1.
Determine input voltage level on the horizontal axis
2.
Read regulated output voltage level on the green curve with values on left vertical axis
3.
The PCS100 AVC-20 output voltage depends on the power factor if the input voltage is below 85%
remaining
The PCS100 AVC-20 Sizing Tool is a software tool which includes detailed performance curves and is an
alternative method for selecting the optimal size of the PCS100 AVC-20 specific to the application.
80%
85%
90%
Figure 2-2: PCS100 AVC-20 performance curve
95%
100%
105%
System kW loading < 75%
System kW loading 100%
110%
115%
120%
PCS100 AVC-20 Input Voltage
13
125%
130%