ABB PCS100 AVC-20 User Manual page 77

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual
Code
Origin
Type
195
M
W
202
R, I
W/AB
209
System
Info
210
System
Info
211
System
Info
212
System
Info
214
System
Info
216
System
Info
217
System
Info
218
System
Info
219
System
Info
220
System
Info
276
R
F
283
R
F
328
M
W
GDM Info
Description
CIOB RS485
CIOB RS485
Timeout
Communications timeout
(Modbus).
Transistor
Rectifier or Inverter
Junction
Transistor Junction model
OverTemp
hot.
Reboot
The system is rebooting,
perhaps after a firmware
upgrade.
Remote
A start, stop or reset
command has been
received from remote
terminal.
Local
A start, stop or reset
command has been
received from the GDM.
Automatic
The system has received an
automatic stop command.
Note: This typically occurs
after a reset.
CanIO
A Mode change command
has been received by
master mux I/O lines
Modbus
A Mode change command
has been received by a
Modbus connected device
Factory
A Mode change command
webpage
has been received by the
internal factory web pages
Remote
A Mode change command
webpage
has been received by the
remote user web pages
Command
A Mode change command
Line
has been received from the
command line
Unknown
A Mode change command
source
has been received from an
unknown source.
RFI relay
RFI relay or driver indicated
error
a problem.
Many
The soft charge contactor
contactor
is switching too often.
activations
SCM Comms
The Master has failed to
lost
receive a response to a
status request from the
SCM.
Recommended Action
Repair external RS485 device
Check all module fans are
operating properly and
ambient temperature is not
too high.
Info only
No action required
Info only
Info only
Info only
Info only
Info only
info only
info only
Info only
Power cycle system and if
problem persists contact ABB
service.
Replace module.
(1) Check the event log for
SCM errors. (2) Check the
power supply to the SCM. (3)
Check VCAN cables and
connections between the
Master and the SCM.