Menu 6 References; Submenu 60 V Setpoint - ABB PCS100 AVC-20 User Manual

Active voltage conditioner
Table of Contents

Advertisement

60
PCS100 AVC-20 User Manual
Parameter:
35 SCM Revision
Function:
Displays the SCM (System Configuration Module) software revision
Parameter:
36 CGI Revision
Function:
Displays the CGI software revision
Parameter:
37 Modbus Revision
Function:
Displays the Modbus software revision
Parameter:
38 NTP Revision
Function:
Displays the NTP (Network Time Protocol) software revision
Parameter:
39 Email Revision
Function:
Displays the Email software revision
8.3.6

Menu 6 References

8.3.6.1

Submenu 60 V Setpoint

60 V Setpoint
The submenu contains parameters for configuring for the output voltage setpoint
Note: This menu is only visible with Tech login
Parameter:
600 V Set Manual
Function:
Sets the target output voltage of PCS100 AVC-20
Access
Tech
Range:
0 to 250%
Default:
Nameplate rating of PCS100 AVC-20
Setting Up:
Set to nominal supply voltage ± 10% (RMS)
Note:
Typically, this parameter is set to the same value as 13 Supply Voltage. If set too close
to
recorded in the event log.
Parameter:
601 V Set Source
Function:
Sets the source of output voltage setting
Access
Tech
Range
Manual / AIN1 / AIN2 / Modbus
Default setting:
MANUAL
Setting Up:
For settings other than Manual the Extended I/O board is required.
Note:
For an AVC without an Extended IO board only manual adjustment of the AVC output
voltage is available.
Note:
Additional parameters in this submenu are related to optional Extended I/O board and are not used
with standard PCS100 AVC-20 operation and thereby not described in this document. Complete
parameter descriptions are shown in separate document related to Extended I/O board.
Table 8-5: Menu 3 Product Revision Parameters
15 Sag Threshold or 16 Surge Threshold spurious sag/surge events may be
Table 8-6: Menu 6 Reference Parameters

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcs100 avc-40

Table of Contents