Replacement Checklists
3-6-1

Pattern A: Mixed Mid-sized and Large PLCs

Checklist 1
Item
Original Unit: C500-LK009-V1
CPU Bus
Not applicable
Unit unit
number
Node
Check setting on pins 1 to 5: [
address
Pins
1 to 5
address
00000
00001
00010
00011
00100
00101
00110
00111
01000
01001
01010
01011
01100
01101
01110
01111
Number of
Check setting on pins 6 to 8 of SW1:
LR Bits
[
] Bits / [
Pins
Pin 3 of SW3
6 to 8
1 (Single-
level LK009)
000
32 bits/
32 (8) Units
001
64 bits/
16 (8) Units
010
128 bits/
8 (4) Units
011
256 bits/
4 (2) Units
100
512 bits/
2 (*1) Units
101
Invalid set-
ting
110
111
50
The pattern A system contains mid-sized (C200H@ or CS-series) PLCs and
large (C500, C1000H, or C2000H) PLCs. Set the replacement PC Link Units
as shown in the following table.
Use the following checklist when replacing a C500-LK009-V1 with a CVM1-
LK401.
]
Node
Pins
Node
1 to 5
address
0
10000
16
1
10001
17
2
10010
18
3
10011
19
4
10100
20
5
10101
21
6
10110
22
7
10111
23
8
11000
24
9
11001
25
10
11010
26
11
11011
27
12
11100
28
13
11101
29
14
11110
30
15
11111
31
] Units
0 (Multi-level)
32 bits/
16 (8) Units
64 bits/
8 (4) Units
128 bits/
4 (2) Units
256 bits/
2 (*1) Units
Invalid setting
Replacement Unit: CVM1-LK401
Any unique number in setting
range (Do not set the same unit
number on two CPU Bus Units in a
PLC.)
Set the CVM1-LK401's node
address to the same node address
that was set on the C500-LK009-
V1. (Set the rotary switches in 2-
digit decimal.)
NODE
No.
0
0
×10
×10
1
Set the same number of LR bits
that was set on the C500-LK009-
V1.
Pins
Pin 3
6 to 8
1 (Single-
0 (Multi-
level LK009)
level)
000
32 bits/
32 bits/
32 Units
16 Units
001
64 bits/
64 bits/
16 Units
8 Units
010
128 bits/
128 bits/
8 Units
4 Units
011
256 bits/
256 bits/
4 Units
2 Units
100
512 bits/
Invalid set-
2 Units
ting
101
Invalid set-
ting
110
111
Section 3-6
Remarks
Do not mount more PC
Link Units than allowed.
Check the node address
settings on other nodes in
the PC Link to confirm
that the same address is
not already taken.
A Unit error will not occur
if the same node address
is set on two PC Link
Units in the same PC
0
Link, but there will be
data errors in the LR
Area.
Make the "number of LR
bits" setting on the polling
node (node 0) in the PC
Link. The "number of LR
bits" settings on the other
nodes (polled nodes) are
ignored.
Set the same level/link
number (next item in
table) that was set on the
Unit being replaced. If an
invalid setting is set, the
max. valid number of bits
setting will be used
instead.
The number of Units
listed in parentheses for
the C500-LK009-V1 is the
maximum number of
Units for the C500 PLC.
The (*1) setting is invalid
for the C500.