Installation Instructions

The zone sensor has been designed for easy installation.
Use the checklists below to assist in the device installation
and configuration process. Performing and verifying the
steps below will prevent or resolve the most common field
installation errors.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

Symbio 400

Remove power from the HVAC equipment and apply electrical
1
lock out/tag out procedures.
2
Symbio 400 controller: Set rotary dials to 0 – 0 – 1.
Connect the 24 Volt AC power wires between the zone sensor
3
and the Symbio 400 controller.
Connect the 2-conductor + shield cable between the zone
sensor and Symbio 400 controller.
4
Note: Communication is polarity sensitive. Ensure that the
wires are landed to the correct terminals.
(Optional) Connect motion sensor or space temperature
5
sensor to zone sensor terminals 17 and 18.
6
Apply power to the HVAC equipment.
7
Proceed to the Zone Sensor Configuration checklist.

ReliaTel BCI-R

Remove power from the HVAC equipment and apply electrical
1
lock out/tag out procedures.
BCI-R control board: Install the jumper wires between J4 -
2
terminals 3 and 4 and Terminator terminals 4 and 5.
3
BCI-R control board: Set rotary dials to 0 - 0 - 1.
4
BCI-R control board: Set the Link slide switch to
RTRM control board: Install a jumper wire between J6 -
5
terminals 1 and 2 when the internal or wired space
temperature sensor is used.
Connect the 24 Volt AC power wires between the zone sensor
6
and RTRM control board.
Connect the 2-conductor + shield cable between the zone
sensor and the BCI-R control board. Connect the shield wire to
7
the RTRM control board.
Note: Communication is polarity sensitive. Ensure that the
wires are landed to the correct terminals.
(Optional) Connect motion sensor or space temperature
8
sensor to zone sensor terminals 17 and 18.
9
Apply power to the HVAC equipment.
10
Proceed to the Zone Sensor Configuration checklist.
Important:
If the HVAC equipment configuration has been
changed, the BCI-R must be reinitialized to make
the additional control data available. See section,
"What To Do After Adding Options or Equipment
to the Unit".
25
BACnet
.
BAS-SVN028K-EN