• Firmware rev – current firmware installed on sensor.
• Room temp. – current air temperature in the space.
• Occupancy state – occupancy state being sent to HVAC equipment unit status.
• Temp. source – location of the space temperature sensor currently in use:
– Internal: Sensor internal to zone sensor.
– Wired: External sensor wired to zone sensor terminals 17 and 18.
– Remote: External sensor wired to HVAC equipment controller.
• OA temp. – outdoor air temperature.
• DA temp. – discharge air temperature.
• RA temp. – return air temperature.
• MA temp. – mixed air temperature.
• RH – indoor relative humidity.
• OA RH – outdoor relative humidity.
Note: Discharge air sensor is an optional sensor for Symbio 800 controlled equipment.
• DA temp. – discharge air temperature.
• RH - indoor relative humidity.
• Econ. available: Yes – OA conditions allow economizing.
• Economizer: On – HVAC equipment currently economizing.
• Cooling: On – HVAC equipment is cooling.
• Primary heat: On – HVAC equipment is heating.
• Secondary heat: On – Secondary heat source is heating.
Note: The Symbio 800 does not support a secondary heat source.
• Cooling – HVAC equipment is cooling.
• Primary heat – HVAC equipment is heating.
• Secondary heat – Secondary heat source is heating.
• Unit status: Indicates if BACnet data is being passed between the HVAC equipment and
the zone sensor.
– Online: data is being passed.
– Offline: data is not being passed.
• MAT low limit: On – economizer is being limited due to low mixed
air temperature. Off – normal temp.
• DAT sensor fail: On – sensor fail. Off – sensor normal.
• OAT sensor fail: On – sensor fail. Off – sensor normal.
• RAT sensor fail: On – sensor fail. Off – sensor normal.
• MAT sensor fail: On – sensor fail. Off – sensor normal.
Note: Symbio 800 does not use the mixed air sensor for economizer control.
• Indicates if BACnet data is being passed between the HVAC equipment and the zone
sensor.
– Online: data is being passed.
– Offline: data is not being passed.
• Econo fail close: On – OA damper is open when it should not be.
Off – normal.
• Econo fail open: On – OA damper is not open when it should be.
Off – normal.
• Blocked OA: On – No outdoor air to equipment. Off – normal.
• Excessive OA: On – excessive outdoor air. Off – normal.
• No items to display.
• Shed input: displays status of dry contact between terminals 16 and 18.
• Shed demand: displays status of BACnet load shed command. Can be modified for testing
purposes. This is the only field that is configurable in Service View.
• Device Name: VTR810xAxxxx-2.
• Graphic Library Revision: 3.0.1.