2.2.3
Fuel Conversion, Revised Fuel
System
The revised fuel system uses a knob that controls a
valve on the regulator to select the fuel type. See
Figure 2-9 and Figure 2-10.
3
1. Fuel selector
2. Fuel inlet
3. Integral fuel solenoid valve
Figure 2-9 Revised Fuel System
2
1. Fuel selector
2. Pressure port
Figure 2-10 Fuel Selection (NG Position Shown)
TP-7091 2/21
Fuel Selection, Revised Fuel System
1. Press the OFF button on the generator set
2. Disconnect utility power to the generator set (open
3. Disconnect the generator set engine starting
1
4. Turn off the fuel supply.
5. To change the fuel selection:
2
GM114166
1
Figure 2-11 Knob Position, NG
GM110973- CMP
controller.
the corresponding circuit breaker in the distribution
panel).
battery, negative (- ) lead first.
a. For natural gas (NG), turn the selection knob all
the way clockwise. The knob lines up with the
UP arrow on the regulator body as shown in
Figure 2-11.
b. For
LPG,
turn
counterclockwise as far as it will go,
approximately ¼ turn. See Figure 2-12.
Img_0899
the
selection
knob
Section 2 Fuel