Siemens SICAM Q80 Operating Instruction page 74

Power quality recorder
Hide thumbs Also See for SICAM Q80:
Table of Contents

Advertisement

E-74
SICAM Q80 7KG8080
15.1.3 Digital inputs
4 digital inputs
Parameter
channels / bits
terminal connections
sampling rate per channel
insulation test voltage
electrical safety
rating
measurement category
degree of pollution
max. input level ue
nom. input level ue
switching level Us
unipolar low
unipolar high
current input
circuit time
low
high
high
low
Description of the
digital inputs of SICAM Q80 7KG8080
15.1.4 Digital outputs
4 digital outputs
Parameter
channel / bits
terminal connection
insulation test voltage
electrical safety
rating /
measurement category
degree of pollution
switching time
max. switching power
switching voltage
max. switching current
contact impedance
Description of the
digital outputs of SICAM Q80 7KG8080
Power Quality Recorder SICAM Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 12.01.2015
typ.
min. / max.
4
screw terminal 14 to 24 AWG
0.2 mm² to 2.5mm²
1 kHz
3.6 kV
RMS
250V / CAT III
2
600 V
230 V
/ 350 V
RMS
DC
<16 V
<14 V
>16.8 V
>18 V
<500 µA
280 µA
70 µs
<180 µs
23 µs
<40 µs
.
38
typ.
min. / max.
4
screw terminal 14 to 24 AWG
0.2 mm² to 2.5mm²
3.6 kV
RMS
250 V / CAT III
2
5 ms
<8 ms
<1000 VA
>1 V
<250 V
DC
< 1 A
<4 A
<50 m
.
38
Test conditions / Remarks.
each isolated
American Wire Gauge
for rigid or flexible line
50 Hz, 10 sec
between channels and chassis
in accordance with EN 61010-1
in accordance with IEC 60664
peak or DC voltage
Schmitt-Trigger-characteristics
Hysteresis 0.04 V typ.
u
= -600 V to +600 V
e
Test conditions / Remarks.
mechanical closer
American Wire Gauge
for rigid and flexible lines
50 Hz Sinus; 10 sec
according EN 61010-1
according IEC 60664
min. switching voltage at 1mA
RMS
250 V~ cos =1.0 ... 0.4
250 V~ cos =1.0

Advertisement

Table of Contents
loading

Table of Contents