Honeywell ADEMCO LYNX XL Series Installation And Setup Manual page 46

Table of Contents

Advertisement

LXL-1010 Installation and Setup Guide
*80 Menu Mode: Defining Output Functions
Use this mode to program output function definitions (up to 24 functions) that provide automated
control of any of the output devices, based on events occurring on individual zones or zones with
certain zone types. Each output definition is identified by an output function number, and includes
the following components:
Output Definition Components
Component
Output Function No.
Activated By
Event
Output Action
Output No.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to
output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt
Output Funct. # = 01 (assuming this is the first output function)
Activated By:
Enter Zn No.
Output Action
Output Number = 02 (device mapped in *79 Menu Mode)
Start Output Definition mode by pressing
prompts are displayed:
∗ ∗ ∗ ∗ 80 Menu Mode
PROMPT
Output Funct. #
(00 = Quit)
01
A E
Trig
?00 0
0
ZL=1
7–2
www.PDF-Zoo.com
Description
A reference number that defines an output's characteristics.
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
Event that triggers the output action. Can be an event occurring on a specific zone
number or a zone list, or a specific zone type.
Defines the action of the X-10 device when the defined event occurs. Can close for 2
seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.),
toggle the device state, or activate for a defined duration (set in data field *177).
Assigns this function to a specific output number (defined in *79 Menu Mode). This is
the output number that will perform this function upon the triggering event. Note that
each defined function is associated with only one output number. This means that if
more than one output device needs to perform this particular function, you need to
define another output function number with the same attributes, but assign the
appropriate output number. (i.e. output devices can be assigned more than one function
number, but each function number can only be assigned a single output number.
Entry
= 3 (zone number)
= 04 (requires 2-digit zone numbers)
= 3 (continuous pulse)
VALID ENTRIES
Output Function No.
01-24 = output function
01
number
[∗] to continue
Summary Screen
[∗] to continue
firealarmresources.com
80 while in Data Programming mode. The following
Q
EXPLANATION
Enter the output function number to be defined (or 00 to exit).
This screen displays a summary of the current output programming
(for this example, Zone List has been selected-this is the default
screen).
A = Output Action; E = Triggering event; Trig = Trigger type
NOTE: A question mark in the summary screen indicates that the
device number shown has not been mapped. Use *79 Menu mode to
map the device.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lxl-1010

Table of Contents