Honeywell WAVE2EX - Ademco Two Tone Siren Installation And Setup Manual

Honeywell WAVE2EX - Ademco Two Tone Siren Installation And Setup Manual

Self-contained, rechargeable wireless control/communicators

Advertisement

ADEMCO LYNXR-I
Security Systems
Installation and Setup Guide
1
2
3
OFF
4
5
AWAY
6
7
8
STAY
9
0
#
AUX
K14114 3/06 Rev. B

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell WAVE2EX - Ademco Two Tone Siren

  • Page 1 ADEMCO LYNXR-I Security Systems Installation and Setup Guide AWAY STAY K14114 3/06 Rev. B...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    Table of Contents SYSTEM FEATURES ..........................4 MOUNTING THE CONTROL........................5 WIRING CONNECTIONS...........................6 CONNECTING/CONFIGURINGCOMMUNICATIONS DEVICES ............8 AC POWER AND BACKUP BATTERY....................11 INSTALLING WIRELESS ZONES......................13 MECHANICS OF PROGRAMMING ......................16 ZONE RESPONSE TYPE DEFINITIONS ....................18 DATA FIELD DESCRIPTIONS ........................20 ✻56 ENHANCED ZONE PROGRAMMING MODE ................29 ✻80 DEVICE PROGRAMMING MENU MODE ..................34 ✻81 ZONE LIST MENU MODE........................37 ✻83 ENHANCED SEQUENTIAL MODE ....................38...
  • Page 4: System Features

    LYNXR-I Installation and Setup Guide System Features LYNXR-I is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N U U U U L L L L LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed. Powerline Carrier Devices have not been evaluated by UL. The LYNXR-I control is a self-contained, rechargeable wireless control/communicators that feature easy installation and usage.
  • Page 5: Mounting The Control

    LYNXR-I Installation and Setup Guide Mounting the Control Wall Mounting The illustration below shows the front assembly separated from the back plate. DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the front assembly board. 1.
  • Page 6: Wiring Connections

    LYNXR-I Installation and Setup Guide Wiring Connections Wiring Overview The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on the inside back cover when making connections. U U U U L L L L External sounders have not been evaluated by UL.
  • Page 7 LYNXR-I Installation and Setup Guide Wiring Connections Make Earth Ground Connection The designated earth ground terminal (1) must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective. The following are examples of good earth grounds available at most installations: Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically connected and secured to which the ground lead is electrically connected and secured.
  • Page 8: Connecting/Configuringcommunications Devices

    LYNXR-I Installation and Setup Guide Connecting/Configuring Communication Modules General This LYNXR-I supports central station reporting via long range radio and internet. It also supports upload/download programming capability via the Internet or a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN.
  • Page 9 LYNXR-I Installation and Setup Guide AlarmNet 7845GSM*, 7845i-GSM*, 7845i-ENT or 7845i, Communications Device The 7845i-ENT/7845i and 7845CV2 can not be used for installations requiring 24-hour standby. 1. Connect the 4-wire communications cable to the LRR/IP Communications port on the LYNXR-I. 2.
  • Page 10 LYNXR-I Installation and Setup Guide LRR/IP Communications Device 24-Hour Standby Power If you are installing the AlarmNet 7845GSM/7845i-GSM or 7845i-L you must install the Super High Capacity battery P/N WALYNX-RCHB-SHA in the LYNXR-I. The 7845i-ENT/7845i and 7845CV2 can not be used for installations requiring 24-hour standby. AlarmNet 7845CV2 1.
  • Page 11: Ac Power And Backup Battery

    LYNXR-I Installation and Setup Guide AC Power and Backup Battery The system is powered by a 9VAC, 25VA Plug-in Transformer, ADEMCO K10145X10 (K10145CN in Canada). Refer to the wiring table below for wire gauge and length. Distance from Transformer Wire Gauge Use only the provided ADEMCO K10145X10 to Control or K10145CN Transformer.
  • Page 12 LYNXR-I Installation and Setup Guide AC Power and Rechargeable Backup Battery The LYNXR-I is equipped with an integral, replaceable, rechargeable battery pack rated at 7.7Vdc. Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Model/Part Number Battery StandbyTime Low Battery Notification...
  • Page 13: Installing Wireless Zones

    LYNXR-I Installation and Setup Guide Installing Wireless Zones General Information Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons. Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
  • Page 14 LYNXR-I Installation and Setup Guide Transmitter Battery Life • Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.
  • Page 15: Series Transmitter Loop Numbers

    LYNXR-I Installation and Setup Guide 5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters) The following illustration shows the compatible transmitters, their associated input types and loop designations. LOOP 3 LOOP 3 LOOP 2 LOOP 4 LOOP 4 LOOP 4 YOU MUST YOU MUST...
  • Page 16: Mechanics Of Programming

    LYNXR-I Installation and Setup Guide Mechanics of Programming General Programming Information Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The system can be programmed at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired.
  • Page 17: Loading Factory Defaults

    LYNXR-I Installation and Setup Guide Interactive Menu Mode Programming (✻56, ✻80, ✻81, ✻83, ✻84, ✻85) (i.e., ✻56). The keypad will display the first of a series of prompts. A detailed [✻] + interactive mode No. Press procedure (with displays of prompts) is provided in later sections of this manual. Interactive Mode Used to Program ✻...
  • Page 18: Zone Response Type Definitions

    LYNXR-I Installation and Setup Guide Zone Response Type Definitions General Information During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Type 00 Zone type 00 is used to program a zone that is not used.
  • Page 19 LYNXR-I Installation and Setup Guide Zone Response Type Definitions Zone type 07 is usually assigned to a zone containing an Emergency button Type 07 (audible emergency). 24-hour Zone Characteristics: Audible • Sends a report to the central station, and provides alarm sounds Alarm externally and at the keypad.
  • Page 20: Data Field Descriptions

    LYNXR-I Installation and Setup Guide Data Field Descriptions Defaults (where applicable) are Indicated in bold text. The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Note that both keypad LEDs flash while in Programming mode. Note: Entering a number other than the one specified will give unpredictable results.
  • Page 21 LYNXR-I Installation and Setup Guide Data Field Descriptions The system will wait the time entered before sounding an ✻ Exit Delay 00-99 = exit delay time in seconds alarm if the exit door is left open after the system has been armed.
  • Page 22 LYNXR-I Installation and Setup Guide Data Field Descriptions All four digits of the Subscriber Account number must be entered in Fields ✻ 43 and ✻ 44. If ten-digit format is selected in ✻ 48 (option 5), all ten digits of the Subscriber Account number must be entered. ✻...
  • Page 23 LYNXR-I Installation and Setup Guide Data Field Descriptions This field is used to select a reporting option as follows: ✻ Split/Dual Reporting Enter: 0 - 5 when reporting to telephone receivers. To Primary To Secondary 6 - 9 when reporting to a pager is desired. 0 = All reports None, unless primary 10 - 13 when reporting to an auxiliary telephone receiver.
  • Page 24 LYNXR-I Installation and Setup Guide Data Field Descriptions RF Jam Detection For Event Logging, Option 2 must be selected. ✻ 0 = no jam detection If the control detects an RF Jam condition, a “FAULT” message 1 = RF jam detection with event logging, but no appears for zone 90.
  • Page 25 LYNXR-I Installation and Setup Guide Data Field Descriptions This will be sent when a low battery condition exists in the ✻ Low Battery Report Code system’s standby battery. (See notes above) This is sent periodically to test that the communicator and ✻...
  • Page 26 LYNXR-I Installation and Setup Guide Data Field Descriptions To ensure that the LYNXR-I properly transmits its reports to the Central Station via the proper channel you must program a Primary Phone Number in Field *41 and/or activate/deactivate the LRR/IP Communications Module in Field *55. The 15-Second Dialer Delay (Burglary), programmed in Field in *50 is independent of the delay selected in Field *77 and applies to both telephone and communications device.
  • Page 27 LYNXR-I Installation and Setup Guide Data Field Descriptions If “0” is entered, user can define a macro function for the AUX key. See ✻ AUX Function/1-Button Paging user manual for description of the use of this key. 0 = Aux key performs defined function If “1”...
  • Page 28 LYNXR-I Installation and Setup Guide Data Field Descriptions ✻ ✻ DOWNLOAD INFORMATION ( This is the phone number the control will use to call back the downloading ✻ Download Call Back Phone Number computer. Enter up to 20 digits as follows: 0–9, # +11 for “ ”, # ✻...
  • Page 29: Enhanced Zone Programming Mode

    LYNXR-I Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes, and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter serial numbers.
  • Page 30: Zone Number

    LYNXR-I Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode While in Program mode, press ✻ 56 to enter Zone Programming Menu Mode. ✻ Refer to the zone assignment table for 56 on the separate programming form. ✻ The following explains the 56 prompts in detail.
  • Page 31 LYNXR-I Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode This prompt can be used to enroll loop number and serial number via Loop number or Loop and Serial RF transmission or the loop number can be enrolled manually. If number (if using RF Learning) using the RF Learning Mode, there is no need to manually enter a 1-4 = loop number for the zone of the transmitter...
  • Page 32 LYNXR-I Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode If “L” is displayed, the serial number for this transmitter has already Enroll mode been entered. It may, however, still be viewed, confirmed (only if in 0 = advance to the VOICE DESCRIPTOR IA LC listen mode), or deleted.
  • Page 33 LYNXR-I Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode ✻ † see 84 Assign Zone Voice Descriptors section for vocabulary index Descriptor 1 Enter [#] + 2-digit vocabulary index number† of Use the [6] or [8] key to advance as described. first descriptor word for this zone.
  • Page 34: Device Programming Menu Mode

    LYNXR-I Installation and Setup Guide ✻ 80 Device Programming Menu Mode Powerline Carrier devices (eg., X10 brand devices) are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications.
  • Page 35 LYNXR-I Installation and Setup Guide ✻ 80 Device Programming Menu Mode The "STOP" programming determines when and under what conditions the device will be de- STOP activated. The following options are available: Upon Restore of a Zone List Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when all the zones in that list restore from a previous fault, trouble, or alarm condition.
  • Page 36 LYNXR-I Installation and Setup Guide ✻ 80 Device Programming Menu Mode The following explains these prompts in detail. The left two columns identify the prompts and list the available entries. The right-most column provides a further explanation of the entries. Note: Entering a number other than one specified will give unpredictable results.
  • Page 37: Zone List Menu Mode

    LYNXR-I Installation and Setup Guide ✻ 81 Zone List Menu Mode While in Program mode, press ✻ 81 to enter Zone List Menu Mode. This mode is used to program zone lists for output devices (programmed in ✻ 80 menu mode) or Chime-by-Zone in Zone List 3. NOTES: •...
  • Page 38: Enhanced Sequential Mode

    LYNXR-I Installation and Setup Guide ✻ 83 Enhanced Sequential Mode By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all other existing data that has been programmed for that zone. Note that the ✻...
  • Page 39 LYNXR-I Installation and Setup Guide ✻ 83 Enhanced Sequential Mode Note: If “L” is displayed, the serial number for this transmitter Enroll mode 0 = advance to next zone to be enrolled has already been entered, however, it may still be confirmed, viewed or deleted.
  • Page 40 LYNXR-I Installation and Setup Guide ✻ 83 Enhanced Sequential Mode This prompt can be used to enroll the transmitter serial number via Serial number RF transmission or manually. If using the RF Learning Mode there Enter transmitter’s 7- digit serial number via RF is no need to manually enter a serial number.
  • Page 41: Assign Zone Voice Descriptors

    LYNXR-I Installation and Setup Guide ✻ 84 Assign Zone Voice Descriptors Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the system announces any event involving a zone number. Each descriptor can consist of up to 3 words.
  • Page 42: Voice Vocabulary Index

    LYNXR-I Installation and Setup Guide ✻ 84 Assign Zone Voice Descriptor VOICE VOCABULARY INDEX ½ second pause SYSTEM WORDS GARAGE 61 PATIO ZERO AC LOSS 49 GUEST ROOM 62 POLICE ZONES ARMED ALARM 18 POOL AWAY ATTIC BYPASSED CHIME 63 REAR DISARMED HALL 19 ROOM...
  • Page 43: Record Custom Voice Descriptors

    LYNXR-I Installation and Setup Guide ✻ 85 Record Custom Voice Descriptors Use this mode to record up to 5 custom voice descriptors. Press ✻ 85 while in Programming mode. Note: Entering a number other than one specified will give unpredictable results. Entering “1”...
  • Page 44: Voice Prompt Programming

    LYNXR-I Installation and Setup Guide Voice Prompt Programming The LYNXR-I features a quick programming mode that allows you to program the system by responding to a series of voice prompts. The Voice Prompt Programming Guide provides you with the information required to use this feature.
  • Page 45 LYNXR-I Installation and Setup Guide Voice Prompt Programming Enter Voice Prompt Programming Mode: (Installer Code + 8 8 8). Follow the voice prompts to advance to the selected item in the Main Programming Menu. Add Sensors Delete Sensors First Central Station Phone Number First Central Station Account Number Second Central Station Phone Number Second Central Station Account Number...
  • Page 46 LYNXR-I Installation and Setup Guide Voice Prompt Programming To Delete Sensors Select Select Sensor to "Delete Sensors" be Deleted Press Press [SELECT] [DELETE] To Add an Emergency Pendant 5AA # (5) Pendant Type Medical Fire Silent Police Police When adding wireless keys, wait 5 seconds between transmissions. To Add a Wireless Key LYNXR-I automatically saves phone and account number data once all available digits are entered.
  • Page 47 LYNXR-I Installation and Setup Guide Voice Prompt Programming All four digits of the Central Station Account number must be entered. If ten-digit format is selected, all ten digits must be entered. To Add Second Central Station Phone Number To Add Second Central Station Account Number Refer to the LYNXR-I Programming Default Tables to view the complete set of Template (default table) selections.
  • Page 48: Remote Programming/Control (Downloading)

    LYNXR-I Installation and Setup Guide Remote Programming/Control (Downloading) General Information The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), a HAYES Modem, and ADEMCO’s Compass Downloader for Windows (as specified below). U U U U L L L L Downloading may only be performed if a technician is at the site.
  • Page 49: Remote Programming Advisory Notes

    LYNXR-I Installation and Setup Guide Remote Programming/Control (Downloading) • Command the system to upload a copy of its resident program to the office. • Set the time • View/Modify • X10/ Scheduling • Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm, zones currently in trouble, and RF sensors with low battery conditions;...
  • Page 50: System Operation

    LYNXR-I Installation and Setup Guide System Operation Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer Code is 4-1-1-2, but may be changed in field ✻ The Installer Code is the only code that can enter Programming mode and also, in normal operation mode, is used to enter the Master Code, which allows access to the normal functions of the system.
  • Page 51: Keypad Functions

    LYNXR-I Installation and Setup Guide System Operation Keypad Functions The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed in the display window. When an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be displayed on the keypad.
  • Page 52: Remote Phone Control Feature

    LYNXR-I Installation and Setup Guide System Operation Press and hold key 2 secs (4 beeps) + To use the defined AUX function: action separated by + terminated by + To define AUX function: FUNCTION Press and hold key 2 seconds (4 beeps) To send message to pager: + [65] To program Follow Me Announcement telephone number...
  • Page 53 LYNXR-I Installation and Setup Guide System Operation U U U U L L L L Audio alarm verification has not been evaluated by UL. Audio Alarm Verification (Two-Way Voice Feature) This feature allows the central station operator to listen, talk to or conduct a two-way conversation with an individual(s) at the premises.
  • Page 54 LYNXR-I Installation and Setup Guide System Operation “Follow Me” Reminder Feature This feature allows the user to schedule a time driven message. When activated the system will dial a phone number, that the installer programs in Field ✻ 46, and deliver a voice message (custom words 72, 73, and 74). The LYNXR-I will immediately begin transmitting the voice message and will repeat the message for 45 seconds.
  • Page 55: System Displays

    LYNXR-I Installation and Setup Guide System Operation System Displays Display Meaning Remote Phone Control feature is active (Appears in place of the clock). System Speaker Phone mode is active (Appears in place of the clock). AC power is present. If not displayed, the system is operating on backup battery power. ALARM System is armed and an intrusion has been detected (also appears during a fire alarm or audible emergency alarm).
  • Page 56: Testing The System

    LYNXR-I Installation and Setup Guide Testing the System Test Mode After installation is completed, the security system should be carefully tested, as follows. 1. With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, press the [ ✻...
  • Page 57: System Communication

    LYNXR-I Installation and Setup Guide System Communication This section provides an explanation of formats this system accommodates for reporting alarms and other system conditions to the central station. The process of a successful transmission consists of both the method of communication between the control panel and the central station receiver, and the actual way the information is sent and displayed at the central station.
  • Page 58 LYNXR-I Installation and Setup Guide System Communication Report 3+1/4+1 Standard 3+1/4+1 Expanded Alarm SSS(S) A SSS(S) A SSSS AZ AAA(A) Z Trouble SSS(S) T SSS(S) T SSSS Tt TTT(T) t Bypass SSS(S) B SSS(S) B SSSS Bb BBB(B) b AC Loss SSS(S) E SSS(S) E SSSS EA C...
  • Page 59: Troubleshooting Guide

    LYNXR-I Installation and Setup Guide Troubleshooting Guide Trouble Conditions The word “FAULT” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that there is a trouble condition in the system. Pressing any key can silence the audible warning sound. Instruct users to call for service immediately upon seeing any of the following messages.
  • Page 60 LYNXR-I Installation and Setup Guide Troubleshooting Guide S y s t e m ( i n c l u d i n g W i r e l e s s ) SYMPTOM POSSIBLE CAUSE REMEDY 1a. Transmitter not properly powered. Check or change transmitter's battery.
  • Page 61: Smoke Detectors

    LYNXR-i Installation and Setup Guide Troubleshooting Guide C o n t r o l SYMPTOM POSSIBLE CAUSE REMEDY The word “AC” is not 1a. Interrupted AC power supply. 1a. Check transformer connection and powerline circuit breaker. displayed. Digital communicator 2a. System in Test mode. 2a.
  • Page 62: Programming Default Tables

    LYNXR-I Installation and Setup Guide Programming Default Tables (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *20 Installer code 4112 4112 4112 4112 *21 Quick arm enable *22 Keypad backlight timeout *23 Forced bypass *24 RF house ID code *25 Powerline carrier device house code *26 Chime-by-zone...
  • Page 63 LYNXR-I Installation and Setup Guide Programming Default Tables (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *90 Event logging *91 Alarm audio verification/remote phone control *92 Number of reports in armed period *93 Flexible call back *94 Download phone number *95 Ring detect count for downloading/remote phone control...
  • Page 64 LYNXR-I Installation and Setup Guide Programming Default Tables ✻56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLES 3 & 4 Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor 3 (RF) 47, 04 (FRONT DOOR) 3 (RF) 33, 04 (BACK DOOR) 3 (RF) 80 (WINDOW) 3 (RF)
  • Page 65: Index

    LYNXR-I Installation and Setup Guide – Index – *56 Enhanced Zone Programming Mode....13, 24, 28, 29 Busy-Standby ................59 * 80 Device Programming........28, 34, 35, 36 Button Transmitters ............13, 14 Button Type ................30 *81 Zone List Menu Mode..........28, 37 Button Zones................
  • Page 66 LYNXR-I Installation and Setup Guide Exit Delay ..............21, 59, 62 Message Center ................51 Exit Delay Restart ............. 21, 51 Modem Comm................59 Exit Door.................. 21 Mounting Base ................5 Exit Error Alarm ..............59 Mute System Announcements ..........51 Exit Error Report Code............24, 62 Exit Warning ................
  • Page 67 LYNXR-I Installation and Setup Guide RF..................... 30 RF (Supervised Rf)..............13 RF House ID Code ............. 20, 62 Technical Support..............70 RF Transmitter Low Battery Report Code......25, 62 Telco Handoff................48 RF Transmitter Low Battery Restore ........62 Temporal Pulse................ 20 RF Transmitter Low Battery Restore Code ......
  • Page 68: Regulatory Agency Statements

    LYNXR-I Installation and Setup Guide Regulatory Agency Statements UL NOTICE: This is a "Grade A" residential system FCC STATEMENT THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
  • Page 69: Limitations Of This System Statement

    LYNXR-I Installation and Setup Guide WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
  • Page 70: Specifications

    You may contact Technical Support via Toll Free Fax. Please include your return fax number. You will receive a reply within 24 hours. Technical Support: ..............1-800-645-7492 (8 a.m.-8 p.m. E.S.T.) FAX FAXBACK Automated Fax Retrieval System:......1-800-573-0153 or 1-516-921-6704 / ext. 1667 World Wide Web Address: ............http:// www.honeywell.com/security - 70 -...
  • Page 71: Summary Of Connections Diagram

    BLACK DEVICES CARRIER POWERLINE YELLOW DATA DATA Notes: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police emergency number.
  • Page 72: Warranty

    Honeywell factory service. Connection of any device(s) to a communicating bus of a Honeywell security system (e.g., keypad bus, polling loop) other than those manufactured or approved by Honeywell shall void this warranty. For warranty service, return product transportation prepaid, to Honeywell Factory Service, 165 Eileen Way, Syosset, New York 11791.

This manual is also suitable for:

Ademco lynxr-i

Table of Contents