Display - Carrier FLOTRONIC II 30GN040-420 Operating And Troubleshooting Manual

Flotronic ii control system reciprocating liquid chillers 50/60 hz with microprocessor controls and electronic expansion valves
Table of Contents

Advertisement

Table 13 — Factory Configuration Keystrokes
To change a configuration enter the new configuration
and press
while on the correct configuration.
SUB-
KEYPAD

DISPLAY

FUNCTION
ENTRY
3 FACTORY
FACT CFG
CFG
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
XXXXXXXX
5 SERVICE
SRV CFG
CFG
XXXXXXXX
XXXXXXXX
REFRIG X
TDTYPE X
OPS X
LPS X
FANTYP X
SH X
MOP X
ZM X
LEGEND
MOP — Maximum Operating Pressure
EXV
— Electronic Expansion Valve
When unit is configured for dual set point, chilled liquid
pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoc-
cupied chilled water set point into effect.
Scheduling —
is used to override any current sched-
ule in effect (for 0-4 hours).
clock for the scheduling function.
to program schedules for specific occupied and unoccupied
periods.
The schedule consists of from one to 8 occupied time pe-
riods, set by the operator. These time periods can be flagged
to be in effect or not in effect on each day of the week. The
day begins at 00.00 and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in effect.
If an occupied period is to extend past midnight, it must be
programmed in the following manner: occupied period must
end at 24:00 hours (midnight); a new occupied period must
be programmed to begin at 00:00 hours.
COMMENTS
FACTORY
CONFIGURATION
CODES
Configuration
Code 1
Configuration
Code 2
Configuration
Code 3
Configuration
Code 4
Configuration
Code 5
Configuration
Code 6
Configuration
Code 7
SERVICE
CONFIGURATION
CODES
Configuration
Code 8
Configuration
Code 9
Refrigerant Type
Pressure Transducer Select
Oil Pressure Set Point
Low Pressure Set Point
Fan Staging Select
EXV Superheat Set Point
EXV MOP Superheat
Z Multiplier
is used to activate a
-
are used
45
Table 14 — Adjustable Field Configurations
FIELD CONFIGURATION
ITEM AND CODES
CCN element address
(Entered by CCN Technician)
CCN Bus Number
(Entered by CCN Technician)
CCN Baud Rate
(Entered by CCN Technician)
Cooler Fluid Select
1 = Water (38 to 70 F
[3.3 to 21 C] Set Point)
2 = Medium Brine (15 to 70 F
[–9 to 21 C] Set Point)
Display Unit Select
0 = English
1 = Metric SI
Delay at Power Up
No. Circuit A Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
No. Circuit B Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
Hot Gas Bypass Select
0 = No Valve
Loading Sequence Select
1 = Equal Circuit Loading
2 = Staged Circuit Loading
Lead/Lag Sequence Select
1 = Automatic
2 = Manual, Circuit A Leads
3 = Manual, Circuit B Leads
Oil Pressure Switch Select
0 = Not Used
1 = Air Cooled
Head Pressure Control Type
0 = Not Used
1 = Air Cooled
Head Pressure Control Method
1 = EXV Controlled
2 = Set Point Control for
Both Circuits
3 = Set Point Control for
Circuit A; EXV Control
for Circuit B
4 = Set Point Control for
Circuit B; EXV Control
for Circuit A
Motormaster Select
0 = None
2 = Indirect Control
Cooling Set Point
Control Select
0 = Single Set Point Control
1 = External Switch
Controlled Set Point
2 = Clock Controlled
Set Point
Cooling Reset Control Select
0 = No Reset
1 = 4-20 mA, Internally Powered
2 = External Temperature
Reset
3 = Return Fluid Reset
4 = 4-20 mA, Externally Powered
External Reset Sensor Select
0 = Thermistor Connected to
Options Module
1 = Obtained Through CCN
Outdoor-Air Sensor Select
0 = Not Selected
1 = Selected
Demand Limit Control Select
0 = No Demand Limiting
1 = Two External Switch Inputs
2 = Internal 4-20 mA Input
3 = CCN Loadshed
4 = External 4-20 mA Input
Ramp Load Select
(Pulldown Control)
0 = Disabled
1 = Enabled
Cooler Pump Interlock Select
0 = No Interlock
1 = With Interlock
Cooler Pump Control Select
0 = Not Controlled
1 = ON/OFF Controlled
Remote Alarm Option Select
0 = Not Selected
1 = Selected
Local/Enable-Stop-CCN
Switch Usage†
0 = Not Allowed
1 = Allowed
LEGEND
CCN — Carrier Comfort Network
EXV — Electronic Expansion Valve
FACTORY
SERVICE
CONFIGURATION
REPLACEMENT
CODE
CODE
001
001
000
000
9600
9600
1 = Standard Models
1
2 = Brine Models
0
0
0
0
0 = 30GN190-210*
0
1 = 30GN040-170*
0 = 30GN040-070,
190-210*
0
1 = 30GN080-170*
0
0
1
1
1
1
0
0
1
0
1
2 = 040,045
1
Brine Units
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0
1
0
0
0
1
1
*And associated modular units.
†For reset of alarms.