Display - Carrier FLOTRONIC II 30GN040-420 Operating And Troubleshooting Manual

Flotronic ii control system reciprocating liquid chillers 50/60 hz with microprocessor controls and electronic expansion valves
Table of Contents

Advertisement

SUBFUNCTION
3 FACTORY
CONFIGURATION (cont)
4 FIELD
CONFIGURATION
To toggle between inputs (Yes/No) Press:
5 SERVICE
CONFIGURATION
LEGEND
CCN — Carrier Comfort Network
EXV
— Electronic Expansion Valve
MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
Table 9 — Keypad Directory (cont)
SERVICE (cont)
KEYPAD ENTRY

DISPLAY

XXXXXXXX
XXXXXXXX
XXXXXXXX
FLD CFG
ENO X
BUS X
BAUD X
FLUID X
UNITS X
DELAY X
NULA X
NULB X
HGB X
SEQT X
LEADT X
OPS X
HEADT X
MM X
CSPTYP X
CRTYP X
ERTYP X
OATSEL X
LSTYP X
RAMP X
LOCK X
CPC X
REMA X
ALRST X
(no) or
SRV CFG
XXXXXXXX
XXXXXXXX
REFRIG X
TDTYP X
OPS X
LPS X
FANTYP X
SH X
MOP X
ZM X
Configuration Code 5
Configuration Code 6
Configuration Code 7
Adjustable Field Configuration
CCN Element Address
CCN Bus Number
CCN Baud Rate
Cooler Fluid Select (water/medium brine)
Display Unit Select (English/Metric)
Delay at Power Up (minutes)
No. Circuit A Unloaders
No. Circuit B Unloaders
Hot Gas Bypass Select (used, not used)
Loading Sequence Select (equal circuit, staged circuit)
Lead/Lag Sequence Type
Oil Pressure Switch Select (enable/disable)
Head Pressure Control Type
(none, air cooled, water cooled)
Motormaster Select
Cooling Set Point Control Select
Cooling Reset Control Select
External Reset Sensor Select
Outdoor-Air Sensor Select
Demand Limit Control Select
Ramp Load Select (enable, disable)
Cooler Pump Interlock Select
Cooler Pump Control Select
Remote Alarm Option Select (yes/no)
Allow Local/Stop/CCN Reset of Alarms (yes/no)
(yes)
Service Configurations
Configuration Code 8
Configuration Code 9
Refrigerant
Pressure Transducer Select
Oil Transducer Set Point (psig)
Low Pressure Set Point (psig)
Fan Staging Select
EXV Superheat Set Point (F)
EXV MOP Set Point (F)
Z Multiplier
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under
expressed as Celsius and pressure will be expressed as kPa.
33
COMMENT
, temperature