Kohler 17RES Manual page 82

Residential/commercial generator sets
Hide thumbs Also See for 17RES:
Table of Contents

Advertisement

10. Install the exhaust system. See Figure 6-25.
a. Install the heat shield onto the alternator
exhaust support.
b. Using new gaskets, connect the engine
exhaust muffler to the engine at the flanges. Do
not final tighten the mounting hardware.
c. Secure the muffler mounting tab to the heat
shield.
d. Torque the nuts securing the engine muffler
flange to the engine to 24 Nm (17.7 ft. lb.).
1
5
1. Engine exhaust muffler
2. Muffler bolts
3. Heat shield
4. Flange connection
5. Heat shield bolts
Figure 6-25 Exhaust System
82
Section 6 Disassembly/Reassembly
3
4
2
ADV-6823
11. Connect the alternator leads inside the controller
box. Refer to the wiring diagrams in Section 7 and
see Figure 6-26.
a. Connect alternator leads 1 and 4 to the line
circuit breaker.
b. Connect alternator leads 2 and 3 to the load
connection stud L0.
c. Single-phase models: Reconnect leads 11 and
44 at quick connects 5 and 6.
Three-phase models: Reconnect leads V7, V8
and V9 at quick connects 5, 6 and 7.
d. Connect brush leads FP and FN and stator
leads 55 and 66 to the SCR module. See the
wiring diagrams in Section 7 for the SCR
module connections.
e. Reconnect all other controller connections that
were removed during disassembly.
12. Check that the generator set master switch is in the
OFF position.
13. Reconnect the generator set engine starting
battery, negative (--) lead last.
14. Reconnect power to the battery charger, if
equipped.
1
3
1. Line circuit breaker
2. Neutral terminal (L0)
3. SCR module
Figure 6-26 Controller
2
GM29253A-F
TP-6519 8/17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

17resl17resnt18res18resl18resnt18tres

Table of Contents