Figure 5-6 Three-Phase Alternator Stator Leads
6. Contact the ohmmeter leads and readjust the
ohmmeter to read zero ohms.
7. Check the cold resistance of the stator windings by
connecting the meter leads to stator leads 1-2, 3-4,
and 55-66.
See Section 1.5, Alternator
Specifications, for stator winding resistances.
Most ohmmeters do not provide accurate readings
below 1 ohm. Low resistance readings (continuity)
and no evidence of shorted windings (heat
discoloration) indicate a stator in good condition.
See Figure 5-7.
Leads
1 and 2
1 and 11
2 and 11
3 and 4
3 and 44
4 and 44
55 and 66
1 and 3, 4, 44, 55, or 66
2 and 3, 4, 44, 55, or 66
3 and 1, 2, 11, 55, or 66
4 and 1, 2, 11, 55, or 66
Any stator lead and ground on stator
housing or frame laminations
Figure 5-7 Continuity Test Results on a Good Stator
(single-phase)
52
Section 5 Component Testing and Adjustment
Leads
1 and 4
2 and 5
3 and 6
7 and 10
8 and 11
9 and 12
55 and 66
1 and 2, 3, 7, 8, or 9
1 and 55
Any stator lead and ground
Figure 5-8 Continuity Test Results on a Good Stator
tp6198
8. If the resistance test proves inconclusive, use a
megohmmeter to test the stator as described in the
next step.
Note: Because
Note: Make sure that all stator leads are
9. Use a megohmmeter to determine whether the
stator is shorted to ground.
a. Apply 500 volts DC to any stator lead and the
Continuity
Yes
b. Repeat the test on the other stator leads until
c. Repair or replace the stator if any reading is
No
(three-phase)
ohmmeter
resistance
readings
readings. Take readings of the rotor and
stator at room temperature.
disconnected
before
megohmmeter test.
stator frame. Perform the megohmmeter test
following the instructions of the megohmmeter
manufacturer.
each coil is tested.
Note: A reading of approximately 500 kOhms
(1/2 megohm) and higher indicates a
good stator.
less than approximately 500 kOhms.
reading of less than 500 kOhms indicates
deterioration of the winding insulation and
possible current flow to ground.
Continuity
Yes
No
accuracy
varies,
are
approximate
running
the
A
TP-6519 8/17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

17resl17resnt18res18resl18resnt18tres

Table of Contents