7-52
7-52
RLCM alarm clearing procedures
RLCM RG
major
Alarm display
CM
.
Indication
A major alarm involving an LCM is indicated by nLCM under the PM
subsystem header with an
Meaning
One of the ringing generator units is in the System busy (SysB) state.
Impact
Service is not affected since a switching of support to a backup ringing
generator (SwRG) automatically occurs. However, if the backup ringing
generator fails, ringing will not be produced.
Common procedures
None
Action
The following flowchart is only a summary of the procedure. Use the
instructions in the step-action procedure that follows the flowchart to clear
the alarm.
297–8351–550 Standard 04.01 August 1999
7-52
MS
IOD
Net
.
.
.
beneath it at the MTC level of the MAP display.
M
PM
CCS
Lns
nLCM
.
.
M
Trks
Ext
Appl
.
.
.