Physical data and electrical data - Model RH
Table I: Physical data - Model RH
30RH
Net cooling capacity*
Net heating capacity**
Operating weight
without hydronic module
with hydronic module
Refrigerant charge R-407C
Compressor
Control system
Refrigerant-water heat exchanger
Net water volume
Water connections (MPT gas)
Maximum water pressure
(unit without hydronic module)
Hydronic module
Pump
Available pressure***
Water inlet connection (MPT gas)
Water outlet connection (MPT gas)
Drain tap coupling (MPT gas)
Closed expansion tank water volume
Water fill system (option)
Inlet/outlet diameter (MPT gas)
Refrigerant-air heat exchanger
Tube diameter
No. of rows
Tubes/row
Fin spacing
Fan
Diameter
No. of blades
Air flow (high speed)
Fan speed (high speed)
*
*The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 C,and air entering the condenser at 35 C.
**
The ratings indicated refer to a condenser entering/leaving temperature of 40/45 C,and air entering the condenser at 7 C d.b.and 6 C w.b.
*** At nominal water flow rate during cooling.
Table II: Electrical data - Model RH
30RH
Power supply
Voltage range
Nominal power input*
Effective power input**
Nominal current drawn*
Effective current drawn**
Maximum power drawn***
Maximum current drawn***
Starting current
Pump power input
*
Based on an outdoor entering air temperature of 35 C db, an evaporator entering water temperature of 12 C and an evaporator leaving water temperature of 7 C, unit without hydronic
module
** The power and current values indicated refer to Eurovent Standard conditions.
*** The power and current values indicated refer to an evaporator leaving water temperature of 10 C and a condenser entering air temperature of 46 C.
017
kW
16.70
kW
18.80
kg
235
kg
255
kg
7.15
One scroll compressor
Pro Dialog-Plus
One plate heat exchanger
l
1.50
inches
1
kPa
1000
Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug,
flow control valve and safety valve.
One single-speed pump
kPa
142
inches
1-1/4
inches
1
inches
1/2
l
8
inches
1/2
One, copper tubes and aluminium fins
inches
3/8
3
52
mm
1.81
Two, axial type with two speeds
mm
500
5
l/s
2222
r/s
12.83
017
V-ph-Hz
400-3-50 / 400-3-50+N
V
360-440
kW
6.21
kW
6.30
A
10.75
A
10.90
kW
7.87
A
13.50
A
87
kW
0.65
021
026
21.60
24.60
24.80
27.80
265
285
285
315
7.84
9.30
1.88
2.16
1
1-1/4
1000
1000
125
155
1-1/4
1-1/4
1
1-1/4
1/2
1/2
8
8
1/2
1/2
3/8
3/8
2
3
60
60
1.81
1.81
610
610
5
5
3611
3111
10.83
11.67
021
026
7.95
9.13
8.10
9.30
14.80
18.70
15.05
19.05
10.8
12.23
20.00
22.50
132
134
0.68
0.89
E N G L I S H
033
29.00
34.00
315
345
11.00
2.82
1-1/4
1000
149
1-1/4
1-1/4
1/2
8
1/2
3/8
4
60
1.81
610
5
3333
11.83
033
11.83
12.00
23.65
24.00
14.95
28.00
139
0.93
GB - 3