GE EPM 3000P Instruction Manual page 39

Three-phase digital volt/amps monitor
Table of Contents

Advertisement

CHAPTER 10
P
G
ROGRAMMING
GROUP 4 contains LM1 and LM2 set limit values for the voltage and amperage scale allowing the user to program
the limits for the following Groups: VOLTS phase-to-neutral, VOLTS phase-to-phase, AMPS A, B, C, and AMPS
neutral.
D
10.1: E
IAGRAM
XAMPLE OF
120
100
80
80
CURRENT
60
(AMPS)
50
40
20
0
A
10.1
T
R
RIP
ELAY
The EPM3000P has two Relays. These relays are linked through the program to Set Limits LM1 and LM2. The user
can program above or below set limits for every reading. When a measurement exceeds a particular value, the set
limit triggers and alerts the user. Each relay is programmed to a separate delay time (see Chapter 8).
NOTE: E
ACH LIMIT CAN BE PROGRAMMED TO TRIGGER THE TWO INTERNAL
.
SECONDARY PROTECTION
GROUP 4: SET LIMITS FOR VOLTS/AMPS
T
10-0: G
4 P
ABLE
ROUP
ROGRAMMING
FUNCTION NUMBER
0.
1.
2.
3.
E.
NOTE: I
T
10-0,
N
ABLE
ALL FUNCTIONS HAVE A TWO PART ENTRY
Part 1: The first switch sets the limit to trip either above or below the limit value.
The second switch sets whether Relay 1 will trip when the condition occurs.
The third switch sets whether Relay 2 will trip when the condition occurs.
Part 2: The second part is the Limit Value.
4: S
L
ROUP
ET
IMITS
LM1/LM2 S
L
, V
ET
IMITS
120
LM1 is triggered
40
LM2 is triggered
B
C
PHASES
F
ORMAT
FUNCTION
LM1/LM2 Set Limits for Volts AN,BN,CN
LM1/LM2 Set Limits for Volts AB,CB,CA
LM1/LM2 Set Limits for Amps A,B,C
LM1/LM2 Set Limits for Amps Neutral
Exit Programming GROUP 4
GE Industrial Systems
& R
ELAYS
A
OLTS AND
MPS
LM1 SET TO
TRIGGER ABOVE
100 AMPS.
LM2 SET TO
TRIGGER BELOW
50 AMPS.
LM1 AND LM2 SET LIMITS
F
C
ORM
DRY CONTACT RELAYS FOR ALARM OR
.
34