GE EPM 3000P Instruction Manual page 32

Three-phase digital volt/amps monitor
Table of Contents

Advertisement

Chapter 7 Global Meter Setup
EXAMPLE 1:
Relay 1 will be "SET" once the reading exceeds 5.00 amps. Relay 1 will be "RESET" once the reading
falls below 5.00 amps.
5 . 0 0 A
0 A
N O P O W E R T O T H E U N I T
1. Enter in GROUP 0, FUNCTION 4, Segment C and D: UP, DOWN
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments B, C, and D: UP, UP, DOWN
EXAMPLE 2: NORMALLY RESET - NON-EVENT CONDITION WILL RESET RELAY
Relay 1 will be "SET" if the instantaneous reading for amps is below 4.00 amps or above 5.00 amps.
Under all other conditions the relay will be "RESET".
NOTE: U
NDER THIS SETUP THE RELAY WILL
5 . 0 0 A
4 . 0 0 A
0 . 0 0 A
N O P O W E R T O T H E U N I T
P
S
:
ROGRAMMING
TEPS
1. Enter in GROUP 0, FUNCTION 4, Segments C and D: UP, UP
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP, UP, DOWN. Value: 5.00
3. Enter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP, DOWN. Value: 4.00
S E T
R E S E T
R E S E T
NOT
ACT AS A PROTECTIVE SWITCH
S E T
R E S E T
S E T
GE Industrial Systems
L 1
.
L M 1
L M 2
R E S E T
27