Internal Circuit Diagram - Omron D4JL-1NFA-C5 Manual

Guard lock safety-door switch
Table of Contents

Advertisement

Connections
■ Indicators

Internal Circuit Diagram

24 VDC
D
O1 (+)
O2 (−)
■ Circuit Connection Example
(Examples for the D4JL-@NF@-@)
• Terminals 11-42 and terminals 21-52 are connected internally and
so connect terminals 12-41 and 22-51 for safety-circuit input. (GS-
ET-19).
E1
(+)
E2
(−)
O1
(+)
Door Open/
LED
closed
Detection
Switch
O2
Lock Monitor Switch
(−)
11
41
42
21
51
52
33
63
64
■ Contact Forms
Indicates conditions where the Key is inserted and the lock is applied. Terminals 42-11 and terminals 52-21 are connected internally (as per BIA
GS-ET-19).
Model
Contacts
(door open/closed detection
and lock monitor)
D4JL-@NF@-@
2NC/1NO+2NC/1NO
D4JL-@PF@-@
2NC/1NO+3NC
D4JL-@QF@-@
3NC+2NC/1NO
D4JL-@RF@-@
3NC+3NC
R
Z
LED
D
12
To safety circuit
22
To safety circuit
34
To control circuit
To control circuit
Contact forms
Lock monitor
Door open/
closed detection
Lock monitor
Door open/
closed detection
41
42
11
51
52
21
63
64
33
Lock monitor
Door open/
closed detection
41
42
11
51
52
21
61
62
33
Lock monitor
Door open/
closed detection
41
42
11
51
52
21
63
64
31
Lock monitor
Door open/
closed detection
41
42
11
51
52
21
61
62
31
• Direct opening contacts used as safety-circuit input are indicated
with the
mark. Terminals 11-12 and terminals 21-22 are direct
opening contacts.
• Do not connect the indicator directly to direct opening contacts. If
indicator is connected in parallel with direct opening contacts, a
short-circuit current may flow in the event that the indicator is
damaged, causing equipment to malfunction.
• Do not switch standard loads for more than 2 circuits at the same
time. Otherwise, the level of insulation may decrease.
• The solenoid terminals have polarity (E1: + and E2: − ). Confirm the
polarity before wiring.
Operating pattern
Lock position
41-12
51-22
12
33-34
63-64
22
Stroke
34
Operation Key insertion
Extraction
completion position
completion position
Lock position
41-12
51-22
12
33-34
61-62
22
Stroke
34
Operation Key insertion
Extraction
completion position
completion position
Lock position
41-12
51-22
12
31-32
63-64
22
Stroke
32
Operation Key insertion
Extraction
completion position
completion position
Lock position
41-12
51-22
12
31-32
61-62
22
Stroke
32
Operation Key insertion
Extraction
completion position
completion position
Guard Lock Safety-door Switch
Remarks
NC contacts 11-12 and 21-22
have a certified direct
opening mechanism (
).
The terminals 41-12, 51-22,
ON
33-34, and 63-64 can be
used as unlike poles.
NC contacts 11-12 and 21-22
have a certified direct
opening mechanism (
).
The terminals 41-12, 51-22,
ON
33-34, and 61-62 can be
used as unlike poles.
NC contacts 11-12, 21-22
and 31-32 have a certified
direct opening mechanism
(
).
ON
The terminals 41-12, 51-22,
31-32, and 63-64 can be
used as unlike poles.
NC contacts 11-12, 21-22,
and 31-32 have a certified
direct opening mechanism
(
).
ON
The terminals 41-12, 51-22,
31-32, and 61-62 can be
used as unlike poles.
D4JL
57