Legend And Notes For Tables 10A And 10C; Legend And Notes For Tables 10B And 10D - Carrier 40RU Installation, Start-Up And Service Instructions Manual

Packaged air-handling units 60 hz with puron (r-410a) refrigerant
Table of Contents

Advertisement

LEGEND
Bhp
Brake Horsepower Input to Fan
ESP
External Static Pressure
NOTES:
1. Maximum allowable fan speed is 1200 rpm for all sizes.
2. Fan performance is based on deductions for wet coil, clean
2--- in. filters, and unit casing. See table at right for factory--- sup-
plied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
LEGEND
ESP
External Static Pressure
NOTES:
1. Maximum allowable fan speed is 20 r/s for all sizes.
2. Fan performance is based on deductions for wet coil, clean
51--- mm filters, and unit casing. See table at right for factory---
supplied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.

Legend and Notes for Tables 10A and 10C

FACTORY- -SUPPLIED PRESSURE DROP — ENGLISH
40RUA*07
40RUQ*07
40RUA*08
40RUQ*08
40RUS*08
40RUA*12
40RUQ*12
40RUS*12
40RUA*14
40RUS*14
40RUA*16
40RUQ*16
40RUS*16

Legend and Notes for Tables 10B and 10D

40RUA*07
40RUQ*07
40RUA*08
40RUQ*08
40RUS*08
40RUA*12
40RUQ*12
40RUS*12
40RUA*14
40RUS*14
40RUA*16
40RUQ*16
40RUS*16
36
AIRFLOW
UNIT
(Cfm)
850
1150
1450
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
FACTORY- -SUPPLIED PRESSURE DROP — SI
AIRFLOW
UNIT
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
PRESSURE DROP
(in. wg)
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
PRESSURE DROP
(Pa)
13
20
28
17
27
38
28
42
56
15
24
33
20
30
42

Hide quick links: