Viessmann Vitotronic 200 Installation And Service Instructions Manual page 88

Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
4C:0
Connection at plug
sÖA1:
Heating circuit pump
4d:1
Connection at plug sL:
Shunt pump
4E:0
Connection at plug
gSA1:
Motor for three-way
mixer for return tem-
perature control
4F:5
Run-on time shunt or
boiler circuit pump
5 min
54:0
Without solar control
unit
55:0
Cylinder heating,
hysteresis ± 2.5 K
88
Possible change
4C:1
Primary pump cylinder
primary system
4C:2
Therm-Control contact
4C:3
Circulation pump
gas/water heat exchan-
ger
4d:2
Boiler circuit pump
4E:1
Motor for three-way mix-
ing valve, cylinder pri-
mary system
4F:0
No pump run-on
4F:1
Run-on time adjustable
to
from 1 to 60 min
4F:60
54:1
With Vitosolic 100;
will be recognised auto-
matically
54:2
With Vitosolic 200;
will be recognised auto-
matically
55:1
Adaptive cylinder heating
enabled (see page 78)
55:2
Cylinder temperature
control with 2 cylinder
temperature sensors
(see page 79)
55:3
Cylinder temperature
controller cylinder pri-
mary system (see
page 80)
flue

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gw1