Viessmann Vitocell 100-B Service Instructions Manual page 13

Table of Contents

Advertisement

LED at the high efficiency circulation pump
LED
Illuminates green
Flashes green in short in-
tervals
Fault indications
Flashes red and green
alternately
Flashes red
LED off
Meaning
Circulation pump in opera-
tion
Circulation pump in stand-
by
Circulation pump is ready
for operation but not run-
ning.
Note
The circulation pump
starts automatically after
the cause of the fault has
been removed.
Circulation pump switched
off (blocked)
Displays and troubleshooting
Cause
Undervoltage (< 160 V~)
Overvoltage (> 253 V~)
Motor temperature too
high
Circulation pump does not
start automatically.
No power.
LED faulty
PCB faulty
Remedy
Check power supply
(195 V~ < U < 253 V~)
Check ambient and heat
transfer medium tempera-
tures
Replacing the circulation
pump
Check connecting cable.
Check whether the circula-
tion pump is running.
Replacing the circulation
pump