Viessmann VITOCELL 100-E Installation And Service Instructions Manual

Viessmann VITOCELL 100-E Installation And Service Instructions Manual

Heating water buffer cylinder

Advertisement

Quick Links

VIESMANN
Installation and service instructions
for contractors
Vitocell 100-E/100-W
Type SVW, SVP/SVPA
Heating water buffer cylinder
For applicability, see the last page
VITOCELL 100-E/100-W
Please keep safe.
5517 175 GB
3/2014

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOCELL 100-E

  • Page 1 VIESMANN Installation and service instructions for contractors Vitocell 100-E/100-W Type SVW, SVP/SVPA Heating water buffer cylinder For applicability, see the last page VITOCELL 100-E/100-W Please keep safe. 5517 175 GB 3/2014...
  • Page 2 Faulty components must be replaced with origi- sate or other causes. Ensure a sufficient supply of nal Viessmann spare parts. combustion air. Instruct system users that subsequent modifications to the building characteristics are not permissible (e.g.
  • Page 3 Installing non-authorised components and making non-approved modifications or con- versions can compromise safety and may inva- lidate the warranty. For replacements, use only original spare parts supplied or approved by Viessmann.
  • Page 4: Table Of Contents

    Index Intended use Installation information Product information ................Vitocell 100-E/100-W, type SVW (200 l capacity) ......■ Vitocell 100-E, type SVP/SVPA (400, 750 and 950 l capacity) ..■ Connections ..................■ Installation sequence Installing the Vitocell ................11 Vitocell with immersion heater, type SVW .......... 11 ■...
  • Page 5 Intended use Intended use The appliance is only intended to be installed and operated in sealed unvented systems that comply with EN 12828 / DIN 1988, or solar thermal systems that comply with EN 12977, with due attention paid to the associated installation, service and operating instruc- tions.
  • Page 6 (immersion Vitocell 100-W: In white heater). Vitocell 100-E, type SVP/SVPA (400, 750 and 950 l capacity) Heating water buffer cylinder for storing heating water Suitable for systems to EN 12828 and DIN 4753. in combination with heat pumps, solar thermal sys- tems, solid fuel boilers and heat recovery.
  • Page 7 Installation information Product information (cont.) Air vent valve (EL) Heating water flow 1 (HV1) to the heating circuits Sensor well 1 (SPR1) for cylinder temperature sensor Heating water flow 2 (HV2) from the heat source Sensor well 2 (SPR2) for cylinder temperature sensor Heating water return 2 (HR2) from the heating circuits Heating water return 1 (HR1)
  • Page 8 Installation information Product information (cont.) Heating water flow 1 (HV1) to the heating circuits/air vent valve (EL) Sensor well 1 (SPR1) for cylinder temperature sensor Heating water flow 2 (HV2) from the heat source Sensor well 2 (SPR2) for cylinder temperature sensor Heating water flow 3 (HV3) / heating water return 1 (HR1) Sensor well (SPR3)
  • Page 9 Installation information Product information (cont.) Type SVPA (750 and 950 l capacity) Thermometer sensor retainer Thermometer (TH) up to 4 pce (accessories) Heating water flow G 1 Return stratification G 1 Heating water return G 1 Fig. 5 Front...
  • Page 10 Installation information Product information (cont.) Heating water flow 1 (HV1) to the heating circuits/air vent valve (EL) Heating water flow 2 (HV2) from the heat source Sensor well (SPR1) for cylinder temperature sensor Thermometer sensor retainer Sensor well 2 (SPR2) for cylinder temperature sensor and thermometer sensor Heating water flow 3 (HV3) / heating water return 1...
  • Page 11: Installation Sequence

    Type SVW 200 l min. 650 mm 6 kW Vitocell 100-E/100-W, type SVW Please note 3. If no immersion heater is being installed, seal the The thermal insulation must not come into con- front female connection with the plug supplied and tact with naked flames.
  • Page 12: Fitting The Thermal Insulation, Type Svp

    Installation sequence Fitting the thermal insulation, type SVP Fitting the lower thermal insulation mat Fig. 8 Please note The thermal insulation must not come into con- tact with naked flames. Exercise caution when welding and brazing. Fitting the thermal insulation jacket Note Ensure that no fleece remnants enter the heating water buffer cylinder through the cylinder connections.
  • Page 13 Installation sequence Fitting the thermal insulation, type SVP (cont.) Fig. 9 Note 2. At the front of the cylinder: Attach 6 clip fasteners to 2 people are required for the following work. the edges of the right and left sections of the insula- tion jacket.
  • Page 14: Fitting The Thermometer, Thermometer Sensor And Cover Strips

    Installation sequence Fitting the thermal insulation, type SVP (cont.) Fitting the thermometer, thermometer sensor and cover strips Fig. 10 Type plate (self-adhesive) Fit the thermal insulation jacket evenly around the cyl- Note inder body by patting it. Slide the thermometer sensor into the clamping bracket at the upper base as far as possible and tighten the wing nut.
  • Page 15: Fitting The Cover

    Installation sequence Fitting the thermal insulation, type SVP (cont.) Fitting the cover Fig. 11 Viessmann logo Fitting the Vitotrans and thermal insulation, type SVPA Please note The thermal insulation must not come into con- tact with naked flames. Exercise caution when welding and brazing.
  • Page 16: Fitting The Lower Thermal Insulation Mat, Aligning The Vitocell

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the lower thermal insulation mat, aligning the Vitocell Fig. 12 Type plate Bag with adjustable feet Insert the adjustable feet into the legs as far as possi- Note ble, then adjust them to level the cylinder. Never extend the adjustable feet beyond a total length of 35 mm.
  • Page 17: Fitting The Thermometer Sensor (If Applicable)

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the thermometer sensor (if applicable) Fig. 13 1. Guide the thermometer sensor through the cover 4. Depending on where the thermometer sensor is to strip and insert the thermometer. be fitted, secure it in the clamping bracket or pull the sensor retainer out of the sensor well.
  • Page 18: Fitting The Vitotrans

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the Vitotrans Fig. 14 Fig. 15 1. Fit the bolts to the cylinder. 3. Wind the nuts onto the bolts until hand-tight. 2. Fit the module.
  • Page 19 Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) DE F Fig. 16 1. Connect heating water flow connection pipe 3. Connect heating water stratification connection pipe connection on the Vitotrans. to connection on the Vitotrans. 4. Connect the pipes to the cylinder connections. 2.
  • Page 20: Fitting The Thermal Insulation Jacket

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the thermal insulation jacket Note Ensure that no fleece remnants enter the heating water buffer cylinder through the cylinder connections. Fig. 17 Note 2. Fit 4 clip fasteners above and 2 clip fasteners 2 people are required for the following work.
  • Page 21: Fitting The Cover Strips

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the cover strips Fig. 18 Type plate (self-adhesive) 1. Tighten the nuts on the bolts. 5. Tap the cylinder thermal insulation towards the front. This reduces the gap between the Vitotrans 2.
  • Page 22: Fitting The Cover

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the cover Fig. 19 Viessmann logo...
  • Page 23: Fitting The Cylinder Temperature Sensor

    Installation sequence Fitting the Vitotrans and thermal insulation,… (cont.) Fitting the cylinder temperature sensor Note The cylinder temperature sensor is supplied in the con- trol unit pack. Fig. 20 Sensor wells for 200 l capacity Sensor wells for 400 l capacity Sensor wells for 750 and 950 l capacity Note Never wrap insulating tape around the sensor.
  • Page 24 Installation sequence Connections on the heating water side (cont.) Permissible temperature 1. Connect all pipework with detachable fittings. Heating water flow: 110 °C 2. Install the flow line with a rise and fit an air vent valve at the highest point. Permissible pressure Operating pressure: 3 bar (0.3 MPa)
  • Page 25 Installation sequence Connections on the heating water side (cont.) Air vent valve (EL) Drain outlet (E)
  • Page 26: Parts List, Type Svw (200 L)

    Thermometer 30 - 120 °C 7819509 7819509 Adjustable foot 7818798 7818798 Top panel 7823447 7822688 Flange insulation 7823572 7823572 VIESSMANN logo (curved) 7819230 7819230 Not shown Installation and service instructions 5538599 5538599 Spray paint Silver White 7819545 7822681 Touch-up paint stick, Vitosilver...
  • Page 27 Parts list, type SVW (200 l) Parts list, type SVW (200 l) (cont.) Fig. 23 Type plate...
  • Page 28: Parts List, Type Svp (400 L)

    Clamping bracket 7819655 Sensor retainer 7819654 Adjustable foot 7818798 Thermometer 30 - 120 °C 7819509 VIESSMANN logo (curved) 7819230 Clip fastener (6 pce) 7835643 Pipe collar (3 pce) 7835767 Pipe collars without hole, not shown 7839961 Installation and service instructions, not shown 5538599 Fig.
  • Page 29: Cylinder Assembly

    7825600 0002 Sensor retainer 7819654 7819654 0003 Vitocell 100-E SVPA type plate 5848673 5848674 0004 Clamping bracket 7819655 7819655 0005 Vitocell 100-E installation and service instructions 5583599 5583599 0006 Plug 7843297 7843297 0006 0002 0004 0003 0005 0001 Fig. 25 Thermal insulation assembly Pos.
  • Page 30 Cover strip 7835742 7835750 0008 Thermometer cover (grey) 7820231 7820231 0009 Thermometer 30 - 120 °C 7819509 7819509 0010 VIESSMANN logo (curved) 7819230 7819230 0011 Cover strip 7835743 7835752 0012 Pipe collar (3 pce) 7835767 7835767 0013 Pipe collar (2 pce)
  • Page 31: Pipework Assembly

    Parts list, type SVPA (750/950 l) Pipework assembly Pos. Component Serial no. (see type plate) 7201937 7201938 Part no. of individual part 0001 Panel with rivet 7839399 7839399 0002 EPP retainer for thermometer 7839400 7839400 0003 Mounting 7839401 7839401 0004 Flow pipe 7839402 7839403...
  • Page 32 Commissioning/service reports Commissioning/service reports Commissioning Service Service date: Service Service Service date: Service Service Service date: Service Service Service date: Service Service Service date:...
  • Page 36 Applicability Serial no. (see type plate) 7248307 7201937 7201938 7459899 7501369 Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB Fax: +49 6452 70-2780 Telephone: +44 1952 675000 www.viessmann.com Fax: +44 1952 675040...