Terminal Strip For Internal Heat Pump Components - Viessmann BW 30 .CS Series Installation And Service Instructions Manual

Table of Contents

Advertisement

Installation sequence
Electrical connections

Terminal strip for internal heat pump components

Note
See position
F
in diagram on page 30.
Terminals
Function
8X1
Compressor 1 motor overload relay
8X3
Compressor 1 safety high pressure
switch
9X1
Compressor 2 motor overload relay
9X3
Compressor 2 safety high pressure
switch
13X6
Electronic expansion valve (EEV), Sie-
mens
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and dam-
age to the appliance.
All sensor and signal leads (0-10 V) must be
shielded with copper braiding and have a mini-
mum cross-section of 0.5 mm
Specified lead type: CV
Sensors, internal
Terminals
Analogue inputs and outputs
14X1
Suction gas temperature sensor Wp
14X2
Evaporator inlet temperature sensor
14X4
Evaporator outlet temperature sensor
14X5
Condenser inlet temperature sensor
14X7
Condenser outlet temperature sensor
15X0
Temperature sensor, casing temperature
15X3
Pressure transmitter, low pressure (-1..18 bar)
15X5
Pressure transmitter, high pressure (0..50 bar)
Sensors, external
Terminals
Analogue inputs and outputs
15X2
Outside temperature sensor
27X1
Temperature sensor, cylinder heating, top
25X6
Output demand, external heat source
36
(cont.)
2
.
6
Explanation
Connection values
Voltage:
24 VDC/230 VAC
Factory-fitted
Connection values
Voltage:
24 VDC/230 VAC
Factory-fitted
Connection values
Voltage:
24 VDC/230 VAC
Factory-fitted
Connection values
Voltage:
24 VDC/230 VAC
Factory-fitted
Factory-fitted
tQ
Note
Pt 1000
Pt 1000
Pt 1000
Pt 1000
Pt 1000
Pt 1000
0-10 V
0-10 V
Note
Pt 1000
Pt 1000
0-10 V