Transport and siting requirements

Anti-vibration base

Site the heat pump on a base prepared on site for the
purpose of noise attenuation and even weight distribu-
tion.
Note
In the case of corner installation, enlarge the base by
the minimum clearances (see chapter "Minimum clear-
ances" on page 14).
Fig. 5
Concrete B25, iron
A
Floor construction, screed
B
Top edge unfinished floor
C
Impact sound insulation as per regulations
D
Pressure points of the adjustable heat pump feet
Type BW 301.CS090, BW 301.CS120, BW 302.CS090 and BW 302.CS110
50
1064
1400
Fig. 6
Pressure point, adjustable foot
ê
Pressure-tested sound insulation layer, approx.
E
10 to 20 mm
Front of the heat pump
F
(cont.)
Pressure-tested sound insulation layer, approx.
E
10 to 20 mm
F
Heat pump
168