Power Supply With Power-Off; Electronic Soft Starter, Type Smc - Viessmann BW 30 .CS Series Installation And Service Instructions Manual

Table of Contents

Advertisement

Power supply
(cont.)
Note
The control circuit must be supplied with power with-
out blocking by the power supply utility, so a sepa-
rate power supply is required for the control circuit.
A separate power supply for the control circuit
necessitates a change to the internal wiring. This
may only be carried out by an electrical contractor
according to the connection diagram.
The control circuit power supply and the cable for the
power-OFF signal can be combined in a single 5-
core cable.

Power supply with power-OFF

Power-OFF without on-site load disconnection (delivered condition)
The power-OFF signal is connected directly to the heat
pump control unit via floating contact. The compres-
sors are shut down when power-OFF is enabled.

Electronic soft starter, type SMC

Electronic soft starter functions:
Monitoring the compressor mains feed
Reducing the compressor starting current during the
starting procedure
Delivered condition:
Rotating field, phase asymmetry: 20 %
Max. operating current of "Imax" compressor:
dependent on compressor output
Overload protection
If the tolerance ranges of the electronic soft starter are
exceeded, the soft starter will automatically separate
the appliance from the mains.
Remove the cause if the relay has responded. The
relay does not need to be reset.
Starting characteristics
The starting characteristics are set at the DIP switches
behind the transparent protective flap of the electronic
soft starter. At the factory, the DIP switches are set to
suit the respective heat pump type.
Prior to commissioning, compare the DIP switch set-
tings with the details in the separate "Connection and
wiring diagram", and adjust if necessary.
Cable lengths in the heat pump plus wall clearance
Control circuit power supply (230 V~ if on
site)
Power circuit power supply (400V~)
Additional connecting cables
Note
Observe the technical connection conditions of the rel-
evant power supply utility.
Installation sequence
3 m
3 m
2 m
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitocal 300-g pro spsBw 301.cs090Bw 302.cs230

Table of Contents