Introduction; Installation Safety Considerations - Carrier AquaForce PUREtec 30XWHPZE 301 Installation, Operation And Maintenance Instructions

Water-cooled liquid chillers and heat pump with r-1234ze(e) or optionally with r-515b refrigerant
Hide thumbs Also See for AquaForce PUREtec 30XWHPZE 301:
Table of Contents

Advertisement

1 - INTRODUCTION

The 30XW-PZE / 30XWHPZE units are designed to cool water
(or brine) for the air conditioning of buildings and industrial
processes.
Prior to the initial start-up of the 30XW-PZE / 30XWHPZE units,
the people involved in the on-site installation, start-up, operation,
and maintenance of this unit must be thoroughly familiar with these
instructions and the specific project data for the installation site 
(Machine room, etc).
They are designed for an operating life of 15 years by assuming a
75% utilisation factor; that is approximately 100,000 operating hours.
This manual provides the necessary information to familiarize
yourself with the control system before performing start-up
procedures. The procedures in this manual are arranged in the
sequence required for machine installation, start-up, operation
and maintenance.
Always ensure that all required safety measures are followed,
including those in this document, such as: wearing protective
clothing (gloves, safety glasses and shoes) using appropriate tools,
employing qualified and skilled technicians (electricians, refrigeration 
engineers)  fully  trained  in  the  use  of  flammable  refrigerants  and 
following local regulations (see annexe E in EN 378 -4 - Guidelines
for repairs of equipment using flammable refrigerants).
To  find  out,  if  these  products  comply  with  European  directives 
(machine safety, low voltage, electromagnetic compatibility,
equipment under pressure etc.) check the declarations of
conformity for these products.
According to ISO-817, R-1234ze(E) is classified in safety
group A2L: lower flammability. One of the characteristic of
this refrigerant is the absence of flammable mixture with air
under 21°C of ambiance and controlled humidity conditions.
However when humidity or temperature goes up, this
refrigerant can become flammable and can represent a
potential danger if flammability risks are not properly
mitigated within the machine room installation.
Local building codes and safety standards shall be followed.
In absence of local codes and standards, please refer to EN-
378 (2012) (Safety requirements for substances classified A2)
or to ISO-5149 (2014) (for substances classified A2L) as a
guide. Customer shall obtain approval from the local building
authorities.
For further details on physical properties, flammability &
toxicity characteristics, hazards Identification, installation
safety requirements, etc, refer to standards such as:
• ASHRAE 34, EN 378, ISO-817 and ISO-5149.
• Safety Data Sheet (SDS) supplied by the refrigerant
manufacturer.
• European union's REACH database (Registration,
Evaluation, Authorisation and Restriction of Chemicals).
As R-1234ze(E) refrigerant is mildly flammable, an ATEX perimeter 
of 0,6 m must be put in place around the machine (see § 3 -
Dimensions, Clearances). No source of ignition must be present
within this zone (see standard EN 378-2, Appendix K).
If  an  ignition  source  is  identified  in  the  hazard  area,  additional 
ventilation is compulsory. Implement a no smoking area around
the machine.
Greyed text does not apply to units equipped with option 330 (Low GWP A1 R-515B refrigerant)

1.1 - Installation safety considerations

The  30XW-PZE  /  30XWHPZE  liquid  chillers  are  classified  as 
"indirect heat exchange system" and are designated to be installed
in a special machinery room (Class C as per ISO-5149 and EN-
378) where only authorized personnel have access, who are
acquainted with general and special safety precautions of the
establishment  and  are  qualified  and  trained  in  monitoring  and 
maintenance. The access limitation device must be installed by
the customer (e.g. cut-off, enclosure). This machine is not intended 
to operate in an ATEX area.
The refrigerant R-1234ze(E) falls into refrigerant safety group A2L
in accordance to ISO-5149 and A2 in accordance to EN-378. No
Charge limitations apply for the level of occupancy is 'C'. Please
refer to these standards for further details. This level needs to be
confirmed by the customer.
After the unit has been received, when it is ready to be installed
or reinstalled, and before it is started up, it must be inspected for
damage. Check that the refrigerant circuit(s) is (are) intact,
especially that no components or pipes have shifted (e.g. following
a shock). If in doubt, carry out a leak tightness check and verify
with the manufacturer that the circuit integrity has not been
impaired. If damage is detected upon receipt, immediately fill a 
claim with the shipping company.
Carrier strongly recommends employing a specialised company
to unload the machine.
It is compulsory to wear personal protection equipment.
Do not remove the skid or the packaging until the unit is in its final 
position. These units can be moved with a fork lift truck, as long
as the forks are positioned in the right place
and direction on the unit.
The units can also be lifted with slings, using only the designated
lifting points marked on the unit.
Use slings or lifting beams with the correct capacity, and always
follow the lifting instructions on the certified drawings supplied with 
the unit. Do not tilt the unit more than 15°.
Safety is only guaranteed, if these instructions are carefully
followed. If this is not the case, there is a risk of material
deterioration and injuries to personnel.
Never cover any protection devices.
This applies to the relief valves in the refrigerant or heat transfer
medium circuits, and the pressure switches.
Ensure that the valves are correctly installed, before operating the
unit.
DO NOT OBSTRUCT ANY PROTECTIVE DEVICES:
This applies to any fusible plugs, rupture disks and valves fitted 
on the refrigerant or heat transfer fluid circuits. Check whether the 
original protection plugs are still present at the valve outlets. These
plugs are generally made of plastic and should not be used. If they
are still present, please remove them. Fit devices at the valve or
discharge piping outlets to prevent the penetration of foreign
bodies (dust, building debris, etc.) and atmospheric agents (water
can form rust or ice). These devices, as well as the discharge
piping, must not impair operation or lead to a pressure drop that
is higher than 10% of the set pressure.
5

Advertisement

Table of Contents
loading

Table of Contents