ACTION Button Operation
Table 2 explains what action the control will take
when the button is pressed for different lengths of
time during the various burner operating states.
Priming the Pump
1. Prepare the burner for priming by
attaching a clear plastic hose over the
bleed port fitting and fully opening the
pump bleed port. Use a suitable container
to collect purged oil.
Failure to bleed the pump properly could
result in unstable combustion, hot gas
puff-back and heavy smoke.
Do not allow oil to spray into a hot combustion
chamber while bleeding air from the pump.
Install a gauge in the nozzle discharge port
tubing or fully open the pump bleed valve to
prevent oil spray from accumulating in the
combustion chamber during the air bleed
procedure.
Ensure that all bubbles and froth are purged
from the oil supply system before tightening the
pump bleed valve.
Ensure that the appliance is free of oil and oil
vapor before starting or resetting the burner.
Table 2 - ACTION Button Operation
Burner State/Status
Lockout (soft)
Lockout (hard)
Valve-On Delay, For Ignition or Carryover
Powered on
Any Except Stand By
Powered on
8
Hot Gas Puff-Back
and Heavy Smoke
Hazard
2. Initiate a call for heat.
3. After the burner starts, press and hold the
ACTION button for 15 seconds until the
yellow light turns on. This indicates that
the button has been held long enough.
4. Release the ACTION button. The yellow light
will turn off and the burner will start up again.
5. At burner start up, click the ACTION
button while the igniter is still on. This will
transition the control to a dedicated Pump
Prime mode, during which the motor,
igniter, and valve are powered for four
minutes. The SYS light will be solid yellow
for the duration of Pump Prime mode.
6. Bleed the pump until all froth and bubbles
are purged. If desired, terminate the call
for heat or hold the ACTION button for
at least one second to exit Pump Prime
mode and return to Standby.
7. At the end of 4 minutes, SYS light will turn
from yellow to green and the control will
automatically return to standby mode.
8. If prime is not established during the four
minute pump prime mode, return to step
5 to re-enter Pump Prime mode. Repeat
steps 5 through 7 until the pump is fully
primed and the oil is free of bubbles.
9. Terminate the call for heat, and the
control will resume normal operation.
Pressing ACTION button
1 Second Tap
15+ Seconds
1 Second Tap
15+ Seconds
1+ Seconds
1 Second Tap
Results
Reset the Control
Reset the Control
Go to pump after pump priming is enabled
per the next step
Enable pump priming, then enters pump
prime mode after next ignition sequence
Exits current state and enters Stand-by,
then keeps burner off while the button
is held
Connect to the myTechician app when
prompted.